535-PROF User's Manual
Chapter 5
51
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
D
1000
4. RSP: LOW
Defines the lowest setpoint value to be accepted from the remote setpoint source.
R
–9999 to 99999.
D
Dependent on
RSP:LO.RNG.
value.
5. RSP: HIGH
Defines the highest setpoint value from a remote setpoint source.
R
–9999 to 99999
D
Dependent on
RSP:HI.RNG.
value
6. TRACKING
Defines whether the local setpoints 1 to 8 will track the remote setpoint.
D
NO
•
YES
7. BIAS LOW
Defines the lowest bias value that may be entered.
R
–9999 to 99999.
Maximum value is
BIAS HIGH.
D
–1000
8. BIAS HIGH
Defines the highest bias value that may be entered.
R
–9999 to 99999.
Minimum value is
BIAS LOW.
D
1000
9. RSP FIXED
Defines what happens if remote setpoint is lost while it is active and then is
restored.
•
REMOTE SP
Returns to remote setpoint when it is restored
D
LOCAL
Local setpoint remains active when RSP is
restored
RETRANS.
1. TYPE:2
Defines what is to be retransmitted for output 2
D
PV
This refers to the linearized process variable
•
SETPOINT
This is the target setpoint
•
RAMP SP
This is the ramping, or actual setpoint, when the
setpoint is ramping
•
CTRL. OUT
This is the control output value
2. LOW RANGE:2
Defines the low end of the range for output 2 in engineering units. Does not appear for
RSP:LOW
(D)
RSP:HIGH
(D)
TRACKING
NO
BIAS LOW
-1000
BIAS HIGH
1000
LO RANGE:2
(D)
RSP: FIXED
LOCAL
RETRANS.
TYPE:2
PV