Controller Set Up
42
Chapter 5
535-PROF User's Manual
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
4. LINEARIZE
Specifies if the PV2 input is to be linearized. Thermocouples and RTD’s are
automatically linearized.
D
NONE
•
SQR. ROOT
Square root linearization is activated.
5. LOW RANGE
Specifies the engineering unit value corresponding to the lowest PV2 input value,
e.g. 4 mA.
R
–9999 to 99999
Max. is
HI RANGE
D
Dependent on the input selection
6. HI RANGE
Specifies the engineering unit value corresponding to the highest PV2 input value,
e.g. 20 mA.
R
-9999 to 99999
Min. is
LOW RANGE
D
Dependent on the input selection
7. FILTER
Setting for the low pass PV2 input filter.
R
0 to 120 seconds
D
0 seconds
8. OFFSET
Defines the offset to PV2 in engineering units.
R
–9999 to 99999
D
0
9. GAIN
Defines the gain for PV2.
R
0.100 to 10.000
D
1.000
10. RESTORE
Defines the control mode when a broken PV2 signal is restored.
D
LAST MODE
•
MANUAL
•
AUTOMATIC
•
START REC.
•
RESUME.REC.
•
HOLD REC.
OFFSET
0
GAIN
1.000
RESTORE
LAST MODE
FILTER
0
HI RANGE
(D)
LINEARIZE
NONE
LOW RANGE
(D)