535-PROF User's Manual
Chapter 5
45
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
D
DIRECT
•
REVERSE
8. P.P. TYPE
Defines the type of position proportioning algorithm. Choose values based on the
process.
Feedback option installed
Feedback option not installed
D
SLIDEWIRE
•
SLIDEWIRE
•
VELOCITY
D
VELOCITY
9. CCW TIME
Defines the time it takes a motor to fully stroke counter clockwise.
R
1 to 200 seconds
D
60 seconds
10. CW TIME
Defines the time it takes a motor to fully stroke clockwise .
R
1 to 200 seconds
D
60 seconds
11. MIN. TIME
Defines the minimum amount of time the controller must specify for the motor to
be on before it takes action.
R
0.1 to 10.0 seconds
D
0.1 seconds
12. S/W RANGE
Specifies the full range resistance of the slide (e.g., 100 ohms)
R
0–1050 Ohms
D
100 Ohms
13. OPEN F/B
Defines the feedback ohm value corresponding to full open (100% output).
R
0 to
S/W RANGE
D
Dependent on
S/W RANGE
value
14. CLOSE F/B
Defines the feedback ohm value corresponding to full close (0% output).
R
0 to
S/W RANGE
D
100 Ohms
15. OUT1 STOP
This defines the stopping point for control output 1 when staging outputs.
R
1 to 100%
D
50%
CLOSE F/B
100
OUT1 STOP
50
P.P. TYPE
(D)
CCW TIME
60
CW TIME
60
MIN. TIME
0.1
S/W RANGE
100
OPEN F/B
(D)