535-PROF User's Manual
Chapter 5
31
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
SOFTWARE MENUS AND PARAMETERS
CONFIG.
1. CTRL. TYPE
Defines the type of control output(s).
D
STANDARD
Standard control output, no special algorithms
•
POS. PROP.
Position proportioning control output
•
STAGED
Staged outputs
•
DUPLEX
Duplex outputs
2. LINE FREQ
Defines the power source frequency.
•
50 HZ
D
60 HZ
3. PV SOURCE
Defines how the PV input is derived from PV1 and PV2.
D
PV1
Use PV1
•
1/2:SWITCH
Use PV1 until contact/com selects PV2
•
1/2:BACKUP
Use PV2 if PV1 is broken
•
PV1–PV2
Use PV1–PV2
•
PV1+PV2
Use PV1+PV2
•
AVG. PV
Use the average of PV1 and PV2
•
HI SELECT
Use PV1 or PV2 (whichever is greater)
•
LO SELECT
Use PV1 or PV2 (whichever is less)
4. REM. SETPT.
Selects function of the remote setpoint.
D
DISABLED
•
ENABLED
5. OUTPUT 2
Defines the function of the second output.
•
ALM/EV:ON
For an alarm or event output
•
ALM/EV:OFF
For an alarm or event output
•
RETRANS.
Retransmission
•
COMM. ONLY
Output addressable only through
communication
D
OFF
Completely deactivates the output
CONFIG.
CTRL. TYPE
STANDARD
LINE FREQ
60 Hz
OUTPUT 2
OFF
PV SOURCE
PV1
REM. SETPT.
DISABLED
NOTE:
PV1 and PV2 can be of different types
and different range.