Controller Set Up
40
Chapter 5
535-PROF User's Manual
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
5. LOW RANGE
Specifies the engineering unit value corresponding to the lowest PV1 input
value, e.g. 4 mA.
R
–9999 to 99999
Max. is
HI RANGE
D
Dependent on the input selection
6. HI RANGE
Specifies the engineering unit value corresponding to the highest PV1 input
value, e.g., 20mA.
R
-9999 to 99999
Min. is LOW RANGE
D
Dependent on the input selection
7. SP LO LIM.
Defines the lowest setpoint value that can be entered from the front panel only.
R
–9999 to 99999
Max. is SP HI LIM. Min. is LOW RANGE
D
Dependent on the
LOW RANGE
value.
8. SP HI LIM.
Defines the highest setpoint value that can be entered from the front panel only.
R
–9999 to 99999
Min. is SP LO. LIM. Maximum is HI RANGE
D
Dependent on
HI RANGE
9. SP RAMP
Defines the rate of change for setpoint changes.
D
OFF
Deactivates this function
R
1 to 99999 units per hour
10. FILTER
Setting for the low pass PV1 input filter.
R
0 to 120 seconds
D
0 seconds
11. OFFSET
Defines the offset to PV1 in engineering units.
R
–9999 to 99999
D
0
SP RAMP
OFF
FILTER
0
OFFSET
0
SP LO LIM.
(D)
SP HI LIM.
(D)
HI RANGE
(D)
CAUTION
!
Set parameter values in the presented
order—dependent parameters are dyna-
mically related and changing values of
one can alter the value of another.
For example, if
SP LO LIM
. is set to 0, and
then thermocouple type is changed to
B
T/C
, the
SP LO LIM
. value will change to
104° (the low limit of a type B
thermocouple).
LOW RANGE
(D)