535-PROF User's Manual
Chapter 5
55
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
2. TRIP DEV.
This defines the deviation from setpoint at which the controller will trip to
automatic.
For
AUTO. TRIP
= RISING PV
For
AUTO. TRIP
= FALLING PV
R
-99999 to 0
R
0 to 99999
D
0
D
0
3. DES. OUTPT.
If a digital input is defined to trip the controller to manual mode, this designates the
output value after the trip.
LAST OUT
means that the output value will be equal to
the last output value while in automatic. Choose values based on the process.
Standard Control
On/Off Control
Velocity Prop Control
•
–5 to 105%
•
ON
•
CW
D
LAST OUT
D
OFF
•
CCW
D
OUTS. OFF
4. POWER UP
This defines the control mode upon power up.
•
MANUAL
•
AUTOMATIC
D
LAST MODE
Will power up in the same mode prior to power
down
•
PRETUNE
Will Pretune on every power up.
(Recommended for TYPE 1 pretune only.)
•
RECIPE
5. PWR. UP:REC.
Selects the recipe to use after power up. Appears only if
POWER UP = RECIPE
.
D
LAST REC.
Last recipe used
R
RECIPE 1 to 20
Select recipe number
6. PWR. UP:RUN
Specified how to use the selected recipe after power up. Appears only if
POWER UP = RECIPE
.
•
START REC.
Start from the beginning of the recipe
D
RESUME REC.
Resume recipe from where it left off before
power down
•
HOLD REC.
Hold recipe from where it left off before power
down
7. PWR. UP: OUT.
Defines the output of the controller if powering up in manual mode. LAST OUT
means the output value will be equal to the last output value while in automatic.
Choose values based on your process.
POWER UP
LAST MODE
DES. OUTPT.
(D)
PWR.UP:OUT.
(D)
PWR.UP:RUN
RESUME REC.
PWR.UP:REC.
LAST. REC.
TRIP DEV.
(D)