Controller Set Up
46
Chapter 5
535-PROF User's Manual
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
16. OUT2 STRT.
Defines the starting point for control output 2 when staging outputs.
R
0 to 99%
D
50%
ALARMS
1. ALM. TYPE:1
Defines the type of alarm for alarm 1.
•
HIGH ALRM.
•
LOW ALARM
•
HIGH/LOW
Separate High & Low alarm setpoints in one
alarm
•
BAND
•
DEVIATION
•
MANUAL
Causes an alarm when in manual control
•
REMOTE SP
Causes an alarm when in Remote Setpoint
•
RATE
Selects a rate-of-change alarm
D
OFF
Deactivates the first alarm
2. ALM. SRC:1
Selects the source of the value being monitored by HIGH, LOW or HIGH/LOW
alarm 1.
D
PV
•
SP
•
RAMP SP
•
DEVIATION
•
OUTPUT
•
PV2
3. ALARM SP:1
Specifies the alarm set point for alarm 1 (except HIGH/LOW)
For
HIGH
or
LOW
alarms:
If
ALM.SRC.:1
= OUTPUT
If
ALM.SRC.:1
= any other type
R
0.0% to 100.0%
R LOW RANGE to HI RANGE
D
0.0%
D
0
For
BAND
alarms:
R
1 to 99999
D
0
For
DEVIATION
or
RATE
alarms:
R
-9999 to 99999
D
0
ALARM SP:1
0.0%
ALARMS
ALM. TYPE:1
OFF
OUT2 STRT.
50
ALM. SRC:1
PV