Install / Wire
535-PROF User's Manual
Chapter 3
11
3.770 (95.76)
3.770 (95.76)
1.180 (29.97)
6.000 (152.40)
7.180 (182.37) OVERALL LENGTH
3.585 (91.06)
PANEL
SIDE
BEZEL
GASKET
3.622 (92.00) MIN.
3.653 (92.80) MAX.
3.622 (92.00) MIN.
3.653 (92.80) MAX.
CUTOUT
FRONT
OUT
1 2
ALM
1 2
5 3 5
CHAPTER 3
INSTALLATION
MOUNTING THE CONTROLLER
The 535-PROF front face is
NEMA 4X rated
(waterproof). To obtain a waterproof
seal between the controller and the panel, follow these directions:
1. The 535-PROF fits in a standard 1/4 DIN cutout. Mount the 535-PROF in
any panel with a thickness from .06 in. to .275 in. (1.5 mm to 7.0 mm).
2.
Figure 3.1 shows the controller and panel dimensions. The panel cutout must
be precise, and the edges free from burrs and waves.
3. Place bezel gasket around the controller case (starting at the back of con-
troller). Then, slide the gasket against the back of the bezel.
4. With the bezel gasket in place, insert the 535-PROF into the panel cutout
from the front of the panel.
5. Slide the mounting collar over the back of the case, as shown in
Figure 3.2.
The collar clip edges will lock with matching edges on the controller case.
6. Insert the four mounting collar screws from the rear of the collar. Gradually
Figure 3.1
Instrument Panel & Cutout Dimensions
Mounting Clip
Collar Screws (1 of 4)
Mounting Collar
Bezel
Figure 3.2
Attaching mounting collar