535-PROF User's Manual
Chapter 5
43
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
CUST. LINR.
Defines a custom linearization curve for PV1, if selected. Points 1 and 15 are
fixed to the low and high end of the input range and require only setting a
corresponding PV value. Points 2 through 14 (the Xth points) require setting both
the input and PV values.
It is not necessary to use all 15 points. Whenever the
XTH INPUT
becomes the
high end of the range, that will be the last point in the linearization table.
1. 1ST. INPUT
Specifies the input signal corresponding to the first point.
D
The low end of the appropriate input range (e.g. 4.00 mA)
2. 1ST. PV
Specifies the engineering unit value corresponding to the first point.
R
–9999 to 99999
D
0
3. XTH. INPUT
Specifies the input signal corresponding to the XTH point (X is 2 to 14).
R
Any value greater than the first input
D
The low end of the appropriate input range (e.g. 4.00 mA)
4. XTH. PV
Specifies the unit value corresponding to the XTH point (X is 2 to 14).
R
–9999 to 99999
D
0
5. 15TH. INPT.
Specifies the input signal corresponding to the 15th point.
R
–9999 to 99999
Minimum is
[XTH-1] INPUT
D
The high end of the appropriate input range (e.g. 20.00 mA)
6. 15TH. PV
Specifies the engineering unit value corresponding to the 15th point.
R
–9999 to 99999
D
0
15TH INPT.
(D)
15TH PV
0
1ST. INPUT
(D)
1ST. PV
0
XTH INPUT
(D)
CUST. LINR.
XTH PV
0