535-PROF User's Manual
Appendix 5
A-15
Specifications
VOLTAGE AND FREQUENCY
Universal power supply: 90 to 250 VAC, 48 to 62 Hz.
NOISE IMMUNITY
Common mode rejection (process input): >120 dB.
Normal mode rejection (process input): >80 dB.
AC line is double filtered and transient protected. Snubbers are
provided for each relay output.
CONSTRUCTION
Case:
black plastic ABS.
Bezel:
black plastic ABS.
Chassis assembly:
plug-in type.
Keys:
silicone rubber with diffusion printed graphics.
NEMA rating:
front panel conforms to NEMA 4X when instrument is
properly installed.
AGENCY APPROVALS
MEMORY RETENTION
Lithium battery maintains all programming for approximately
ten years.
EEPROM maintains calibration data indefinitely.
SECURITY
There are two levels of access: restricted and full. A
configurable code is used to enter the full access level.
Functions not available in the restricted level are configurable.
PROFILE CONTROLLER OPTION
When a 535 is specified as a profile controller, the
SET PT
(setpoint) key is replaced at the factory with a
RUN
key to
facilitate operation. Setpoint access is available through use of
the
DISPLAY
key. All functions are described in the manual.
The 535 with profile option provides full ramp and soak
capability with the following features:
DIGITAL DISPLAYS
Upper display:
Five-digit, seven-segment. Used exclusively for
displaying the process variable value. Height is 15 mm (0.6
in.).
2nd display:
nine-character, 14-segment alphanumeric. Used
for displaying setpoint, deviation, output value, slidewire
position (actual valve position) and configuration information.
Height is 6 mm (0.25 in.).
3rd display:
nine-character, 14-segment alphanumeric. Used
for indicating which loop is displayed and for displaying alarm
messages and configuration information. Height is 6 mm (0.25
in.).
All displays are vacuum fluorescent. Color is blue-green.
STATUS INDICATORS
There are two types of indicators: icons and illuminated keys.
ALM 1 and ALM 2 icons:
alarm 1 and alarm 2 status.
OUT 1 and OUT 2 icons:
control output 1 and control output 2 status.
MAN key illuminated:
controller is in manual control mode.
ACK key illuminated:
alarm may be acknowledged.
RUN key illuminated:
a recipe is active.
MENU key illuminated:
controller is in configuration mode.
DIMENSIONS
Meets 1/4 DIN designation as specified in DIN standard number
43 700.
See diagram for details.
MOUNTING
Panel-mounted.
WIRING CONNECTIONS
29 screw terminals in the rear of the instrument.
POWER CONSUMPTION
15 VA at 120 VAC, 60 Hz (typical).
WEIGHT
Approximately 1 kg (2.2 lbs.).
AMBIENT TEMPERATURE
Operative Limits:
0 to 50°C (32 to 122°F).
Storage Limits:
–40 to 70°C (–40 to 158°F).
RELATIVE HUMIDITY
10 to 90% non-condensing.
(Heavy Industrial)
(Available as an option)