Controller Set Up
38
Chapter 5
535-PROF User's Manual
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
EVT.:3 OUT.
NONE
3. RAMP UNIT
Defines ramp segment terms.
D
TIME
•
RATE
4. SP START
Defines initial value for the first ramp segment’s setpoint.
•
IDLE SP the IDLE SP is the first value
D
PV The starting value will be adjusted to account for
the initialPV value
5. GUAR. SOAK
Selects whether guaranteed soak is used during each soak segment.
D
OFF guaranteed soak will not occur
• START SEG. guaranteed soak can occur only at the start of a
soak segment
• WHOLE SEG. guaranteed soak can occur at the start of or at
anytime during a soak segment
6. EVT.:1 OUT.
Selects which output is assigned to event 1. To assign a numerical value (non-
default), the corresponding output needs to be set to ALM/EV:ON or ALM/EV:OFF.
D
NONE
•
2
•
3
•
4
7. EVT.:2 OUT.
Selects which output is assigned to event 2. To assign a numerical value (non-de-
fault), the corresponding output needs to be set to ALM/EV:ON or ALM/EV:OFF.
D
NONE
•
2
•
3
•
4
8. EVT.:3 OUT.
Selects which output is assigned to event 3. In order to assign a numerical
value (non-default), the corresponding output needs to be configured as ALM/
EV:ON or ALM/EV:OFF.
D
NONE
•
2
•
3
•
4
RAMP UNIT
TIME
SP START
PV
EVT.:1 OUT.
NONE
EVT.:2 OUT.
NONE
GUAR.SOAK
OFF