CHAPTER 6
TUNING
OVERVIEW
The self tune function of the 535 consists of two distinct components — Pretune
and Adaptive Tune. In addition, you may choose from three type of Pretune:
TYPE 1 -
for slow thermal processes.
TYPE 2 -
for fast fluid or pressure processes.
TYPE 3 -
for level control applications.
You choose the type of Pretune in the
SELF TUNE
menu.
The Pretune and Adaptive Tune components may be used separately or together.
On the following pages is the step by step guide to the
TUNING
menu paramters.
Figure 6.1
Access the Tuning Menu Block
NOTE:
For more information about Pretune
and Adaptive Tune, refer to section
on Tuning applications in Chapter 7.