Controller Set Up
48
Chapter 5
535-PROF User's Manual
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
10. MESSAGE:1
A 9-character message associated with alarm 1. To enter message: The first
character of third display will be flashing. Press the
and
keys to scroll
through the character set. Press
FAST
key to advance to subsequent
characters. Press the
MENU
to advance to next parameter.
D
ALARM 1.
11. ALM. TYPE:2
Defines the type of alarm for alarm 2.
•
HIGH ALRM.
•
LOW ALARM
•
HIGH/LOW
Separate High & Low alarm setpoints in one
alarm
•
BAND
•
DEVIATION
•
MANUAL
Causes an alarm when in manual control
•
REMOTE SP
Causes an alarm when in Remote Setpoint
•
RATE
Selects a rate-of-change alarm
D
OFF
Deactivates the first alarm
12. ALM. SRC:2
Selects the source of the value being monitored by
HIGH
,
LOW
or
HIGH/LOW
alarm 2.
D
PV
•
SP
•
RAMP SP
•
DEVIATION
•
OUTPUT
•
PV2
13. ALARM SP:2
Specifies the alarm set point for alarm 2 (except HIGH/LOW)
For
HIGH
or
LOW alarms:
If
ALM.SRC.:2
= OUTPUT
If
ALM.SRC.:2
= any other type
R
0.0% to 100.0%
R LOW RANGE
to
HI RANGE
D
0.0%
D
0
For
BAND
alarms:
R
1 to 99999
D
0
For
DEVIATION
or
RATE
alarms:
R
-9999 to 99999
D
0
ALARM SP:2
(D)
ALM.SRC.:2
PV
ALM. TYPE:2
OFF
MESSAGE:1
ALARM 1