535-PROF User's Manual
Chapter 5
47
Controller Set Up
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
4A. HIGH SP:1
Specifies the high alarm set point for alarm 1 of type HIGH/LOW.
If
ALM.SRC.:1
= OUTPUT
If
ALM.SRC.:1
= any other type
R
0.0% to 100.0%
R LOW RANGE
to
HI RANGE
D
0.0%
D
0
4B. LOW SP:1
Specifies the low alarm set point for alarm 1 of type HIGH/LOW.
If
ALM.SRC.:1
= OUTPUT
If
ALM.SRC.:1
= any other type
R
0.0% to 100.0%
R LOW RANGE
to
HI RANGE
D
0.0%
D
0
5. DEADBAND:1
Defines the deadband for alarm 1.
If
ALM.SRC.:1
= OUTPUT
If
ALM.SRC.:1
= any other type
R
0.1% to 100.0%
R
1 to 99999
D
2
D
2
6. ALM.:1 OUT.
Selects the output number for alarm 1.
D
NONE
•
2
•
3
•
4
7. LATCHING:1
Defines the latching sequence of alarm 1.
D
LATCH
•
NO LATCH
8. ACK.:1
Defines whether alarm 1 may be acknowledged.
D
ENABLED
Allows the alarm to be acknowledged
•
DISABLED
Prevents the alarm from being acknowledged
while in alarm condition
9. POWER UP:1
Defines how alarm 1 will be treated on power up.
D
NORMAL
Alarm depends on process variable
•
ALARM
Always power up in alarm regardless of PV
•
DELAYED
Must leave alarm condition and reenter before
activating the alarm
POWER UP:1
NORMAL
ACK.:1
ENABLED
ALM.:1 OUT
NONE
DEADBAND:1
2
HIGH SP:1
0.0%
LOW SP:1
0.0%
LATCHING:1
NONE