535-PROF User's Manual
Chapter 6
73
Tuning
Access Set Up
Return to Operation
Next menu
Next parameter
Next value
Access Tuning
Return to Operation
+
FAST
MENU
DISPLAY
+
FAST
MENU
MENU
▲
▼
MENU
DISPLAY
7. RATE:1
Defines the derivative time for PID set 1.
R
0 to 600 seconds
D
1 second
8. MAN. RST.:1 (or LOADLINE:1)
Defines the manual reset for PID set 1. If using automatic reset, then this
specifies the load line out value.
R
0 to 100%
D
0%
9. CYCLE TM.:1
Defines the cycle time for control output 1 when using a time proportioning out-
put.
R
0.3 to 120.0 seconds
D
15.0 seconds
10. DEADBAND:1
Defines the dead band for control output 1 when using on/off control.
R
1 to 99999 in engineering units
D
2
11. P. PROP. D.B
.
Defines the dead band setting for a slidewire position proportioning output.
R
0.5 to 10.0%
D
2.0%
12A. PID OFST.:1
For duplex applications, defines the offset for the first output.
R –50.0% to 50.0%
D 0.0%
12B. ON OFST.:1
For On/Off applications, defines the offset for the first output.
R
-9999 to 99999 in engineering units
D
0
13A. PID OFST.:2
For duplex applications, defines the offset for the second output.
R
–50.0% to 50.0%
D
0.0%
13B. ON OFST.:2
For On/Off applications, defines the offset for the second output.
R
-9999 to 99999 in engineering units
D
0