IX
Troubleshooting ]
- 205 -
HWE07010
GB
1. Error
Code
Model setting error
2. Error source, cause, check method and remedy
1. Error
Code
Model setting error (Open detection)
2. Error source, cause, check method and remedy
1. Error
Code
Incompatible units
2. Error
definition and error detection method
The check code will appear when the indoor units with different refrigerant systems are connected.
3. Error source, cause, check method and remedy
7113
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring failure
1)
Control board connector
Check the CNTYP2,4,5 connector connection.
Inverter board connector
Check the CNTYP connector connection(P300 - P450
models only)
(2)
Disconnected connector, short cir-
cuit, contact failure
2)
Check the compatibility of the circuit board, and replace
it with a correct one if necessary.
(3)
Incompatibility between the control
board and inverter board (Replace-
ment of the circuit board with the
wrong one)
3)
Check the model selection switch on the outdoor unit
(Dipswitch SW5-7 on the control board.).
7117
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring failure
1)
Control board connector
Check the CNTYP2,4,5 connector connec-
tion.
Inverter board connection
Check the CNTYP connector connection
(P300 - P450 models only)
(2)
Disconnected connector, short circuit, contact
failure
7130
Error source
Cause
Check method and remedy
Outdoor unit
The connected indoor unit is for use with R22
or R407C. Incorrect type of indoor units are
connected.
The M-NET connection adapter is connected
to the indoor unit system in a system in which
the Slim Model (A control) of units are con-
nected to the M-NET.
Check the connected indoor unit model.
Check whether the connecting adapter for
M-NET is not connected to the indoor unit.
(Connect the connecting adapter for M-NET
to the outdoor unit.)
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...