VIII
Test Run Mode ]
- 122 -
HWE07010
GB
Operation
Outdoor unit model
PUHY-P550YSHM-A
PUHY-P250YHM-A
PUHY-P300YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C [81°F/66°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion
6
Model
-
20/100/100/100/125/125
Piping
Main pipe
m [ft]
5 [16-3/8]
Branch pipe
10 [32-3/4]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
25 [55]
Outdoor
unit
Electric current
A
29.4
Voltage
V
400
Compressor frequency
Hz
65
71
LEV open-
ing
Indoor unit
Pulse
222/325/325/325/387/387
SC (LEV1)
159
237
LEV2
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
3.10/0.78 [450/113]
3.10/0.74 [450/107]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
91 [196]
89 [192]
Heat exchanger out-
let (TH3)
47 [117]
47 [117]
Accumulator inlet
7 [45]
7 [45]
Accumulator outlet
7 [45]
7 [45]
SCC outlet (TH6)
27 [81]
27 [81]
Compressor inlet
19 [66]
19 [66]
Compressor shell
bottom
42 [108]
42 [108]
Indoor
unit
LEV inlet
19 [66]
Heat exchanger
outlet
6 [43]
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...