VII
Control ]
- 82 -
HWE07010
GB
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Switch setting is required on any one of OC, OS1 and OS2.
B: The switch on the all of OC, OS1 and OS2 must be set to the same settings.
C: The switch on OC, OS1 and OS2 must be set individually.
3) Refer to "VII [2] Controlling the Outdoor Unit" for details.(page 87)
Switch
Function
Function according to switch setting
Switch setting timing
Units that re-
quire switch
setting
Note.2
OFF
ON
OFF
ON
OC
OS
SW3
1
Test run mode: en-
abled/disabled
SW3-2 disabled
SW3-2 enabled
Anytime after power on
A
-
2
Test run mode: ON/
OFF
Stops all ICs
Sends a test-run
signal to all IC
After power on and when
SW3-1 is on.
A
-
3
Defrost start temper-
ature (Note 3)
P200 - P300
EP200
-10°C [14°F]
-5°C [23°F]
Anytime after power on
B
B
P350 - P450
EP300
-8°C [18°F]
4
Defrost end temper-
ature (Note 3)
P200 - P300
EP200
10°C [50°F]
P200 - P300
EP200
15°C [59°F]
Anytime after power on
(except during defrost op-
eration)
B
B
P350 - P450
EP300
7°C [45°F]
P350 - P450
EP300
12°C [54°F]
5
-
-
-
-
-
-
6
-
-
-
-
-
-
7
-
-
-
-
-
-
8
-
-
-
-
-
-
9
Model setting
Outdoor standard
static pressure
Outdoor high static
pressure
Before being energized
C
C
10
Model setting
High static pressure
60Pa
High static pressure
30Pa
Before being energized
C
C
SW4
1
-
-
-
-
-
-
2
-
-
-
-
-
-
3
Refrigerant amount
adjustment
Normal operation
mode
Refrigerant amount
adjust mode
Anytime after being ener-
gized (except during ini-
tial startup mode.
Automatically cancelled
90 minutes after com-
pressor startup)
A
-
4
Low-noise mode/
step demand switch-
ing (Note 3)
Low-noise mode
Step demand mode Before being energized
C
C
5
-
-
-
-
-
-
6
Cumulative com-
pressor operation
time data deletion
Cumulative com-
pressor operation
time data is re-
tained.
Cumulative com-
pressor operation
time data is delet-
ed.
Anytime after power on
(when the unit is turned
on)
C
C
7
-
-
-
-
-
-
8
-
-
-
-
-
-
9
-
-
-
-
-
-
10
-
-
-
-
-
-
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...