VIII
Test Run Mode ]
- 147 -
HWE07010
GB
Operation
Outdoor unit model
PUHY-P1000YSHM-A
PUHY-P300YHM-A
PUHY-P300YHM-A
PUHY-P400YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ - [68°F/ - ]
Outdoor
7°C/6°C [45°F/43°F]
Indoor
unit
No. of connected
units
Unit
8
No. of units in opera-
tion
8
Model
-
250/250/200/125/63/63/32/25
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
85 [278-13/16]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
45 [ 99 ]
Outdoor
unit
Electric current
A
53.1
Voltage
V
400
Compressor frequency
Hz
88
88
88
LEV open-
ing
Indoor unit
Pulse
400/400/332/406/455/455/254/229
SC (LEV1)
0
LEV2
1400
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.90/0.62
2.90/0.62
2.91/0.60
[421/90]
[421/90]
[422/87]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
82 [ 180 ]
82 [ 180 ]
89 [ 192 ]
Heat exchanger out-
let (TH3)
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Accumulator inlet
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Accumulator outlet
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Compressor inlet
-3 [ 26 ]
-3 [ 26 ]
-4 [ 25 ]
Compressor shell
bottom
30 [ 85 ]
30 [ 85 ]
40 [ 104 ]
Indoor
unit
LEV inlet
39 [ 102 ]
Heat exchanger
outlet
80 [ 176 ]
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...