1) SW4-4: OFF (Compressor ON/OFF, Silent mode (Night mode))
*1. When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON , this function cannot be used.
*2. This function and the 4 levels or 8 levels on-DEMAND function can be used together. Input the order to CN3D 1-2P on the
outdoor unit whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND)
(*3)
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND)
(*3, *4)
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
*4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
CN3D 1-3P
Compressor ON/OFF
*1
Open
Compressor ON
Short-circuit
Compressor OFF
CN3D 1-2P
Silent mode
*2
Open
OFF
Short-circuit
ON
CN3D 1-2P
CN3D 1-3P
Open
Short-circuit
Open
100% (No DEMAND)
75%
Short-circuit
0% (Compressor OFF)
50%
8 levels of on-DEMAND
No.2 CN3D
1-2P
Open
Short-circuit
No.1 CN3D
1-2P
1-3P
Open
Short-circuit
Open
Short-circuit
Open
Open
100%
50%
88%
75%
Short-circuit
50%
0%
38%
25%
Short-circuit
Open
88%
38%
75%
63%
Short-circuit
75%
25%
63%
50%
If the step listed as the wrong example above is taken, thermo may go off.
The percentage of the demand listed in the table above is an approximate value based on the
compressor volume and does not necessarily correspond with the capacity.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
Demand control
steps
Note the following steps to be taken when using the STEP DEMAND
(Example) When switching from 100% to 50%
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...