VIII
Test Run Mode ]
- 110 -
HWE07010
GB
3. Amount of refrigerant to be added
The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units.
The amount necessary for extended pipe (field piping) is not included and must be added on site.
(1) Calculation formula
The amount of refrigerant to be added depends on the size and the length of field piping. (unit in m[ft])
Round up the calculation result to the nearest 0.01kg. (Example: 18.04kg to 18.1kg)
Round up the calculation result in increments of 4oz (0.1kg) or round it up to the nearest 1oz.
(Example: 178.21
oz
to 179oz)
Outdoor unit model
P200
P250
P300
P350
P400
P450
Amount of pre-charged refrigerant in
the outdoor unit (kg)
6.5
9.0
9.0
11.5
11.5
11.5
Amount of pre-charged refrigerant in
the outdoor unit [lbs-oz]
141-5
191-13
191-13
251-6
251-6
251-6
Outdoor unit model
EP200
EP300
Amount of pre-charged refrigerant in
the outdoor unit (kg)
9.0
11.5
Amount of pre-charged refrigerant in
the outdoor unit [lbs-oz]
191-13
251-6
Amount of added refrigerant (kg) = (0.29x L
1
) + (0.2 x L
2
) + (0.12 x L
3
) + (0.06 x L
4
) + (0.024 x L
5
) +
α
Amount of added refrigerant (oz) = (3.12x L
1
' ) +(2.15 x L
2
' ) + (1.29 x L
3
' ) + (0.65 x L
4
' ) + (0.26 x L
5
' ) +
α
L
1
: Length of ø19.05 [3/4"] liquid pipe (m)
L
2
: Length of ø15.88 [5/8"] liquid pipe (m)
L
3
: Length of ø12.7 [1/2"] liquid pipe (m)
L
4
: Length of ø9.52 [3/8"] liquid pipe (m)
L
5
: Length of ø6.35 [1/4"] liquid pipe (m)
α
,
α
' : Refer to the table below.
L
1
' : Length of ø19.05 [3/4"] liquid pipe [ft]
L
2
' : Length of ø15.88 [5/8"] liquid pipe [ft]
L
3
' : Length of ø12.7 [1/2"] liquid pipe [ft]
L
4
' : Length of ø9.52 [3/8"] liquid pipe [ft]
L
5
' : Length of ø6.35 [1/4"] liquid pipe[ft]
Total capacity of
connected indoor units
α
(kg)
α
'(oz)
-
80
2.0
71
81
-
160
2.5
89
161
-
330
3.0 106
331
-
390
3.5
124
391
-
480
4.5 159
481
-
630
5.0
177
631
-
710
6.0
212
711
-
800
8.0
283
801
-
890
9.0
318
891
-
1070
10.0
353
1071
-
1250
12.0
424
1251
-
14.0
494
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...