[
VIII
Test Run Mode ]
- 139 -
HWE07010
GB
3. 3-unit
combination
(1) Cooling operation
Operation
Outdoor unit model
PUHY-P950YSHM-A
PUHY-P250YHM-A
PUHY-P300YHM-A
PUHY-P400YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C [81°F/66°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
8
No. of units in opera-
tion
8
Model
-
250/200/200/125/100/32/32/25
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
85 [278-13/16]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
42 [ 93 ]
Outdoor
unit
Electric current
A
49.2
Voltage
V
400
Compressor frequency
Hz
65
84
84
LEV open-
ing
Indoor unit
Pulse
388/324/324/387/325/261/261/222
SC (LEV1)
130
141
116
LEV2
1400
1400
1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
3.06/0.79
2.95/0.81
2.86/0.76
[444/115]
[428/117]
[415/110]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
89 [ 193 ]
96 [ 204 ]
95 [ 202 ]
Heat exchanger out-
let (TH3)
49 [ 119 ]
47 [ 117 ]
46 [ 114 ]
Accumulator inlet
7 [ 45]
7 [ 45 ]
7 [ 45 ]
Accumulator outlet
7 [ 45 ]
7 [ 45 ]
7 [ 45 ]
SCC outlet (TH6)
27 [ 80 ]
25 [ 77 ]
24 [ 75 ]
Compressor inlet
19 [ 67 ]
19 [ 67 ]
19 [ 67 ]
Compressor shell
bottom
47 [ 117 ]
56 [ 132 ]
47 [ 117 ]
Indoor
unit
LEV inlet
19 [ 65 ]
Heat exchanger
outlet
6 [ 42 ]
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...