VIII
Test Run Mode ]
- 115 -
HWE07010
GB
[7] Standard Operation Data (Reference Data)
1. Single
unit
(1) Cooling operation
Operation
Outdoor unit model
PUHY-P200YHM-A
PUHY-P250YHM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/19°C [81°F/66°F]
27°C/19°C [81°F/66°F]
Outdoor
35°C/ - [95°F/ - ]
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
2
2
No. of units in opera-
tion
2
2
Model
-
100/100
125/125
Piping
Main pipe
m [ft]
5 [16-3/8 ]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
10 [32-3/4 ]
Total pipe length
25 [82]
25 [82]
Fan speed
-
Hi
Hi
Amount of refrigerant
kg
[lbs-oz]
11 [24]
11 [24]
Outdoor
unit
Electric current
A
9.1
12.3
Voltage
V
400
400
Compressor frequency
Hz
52
65
LEV open-
ing
Indoor unit
Pulse
325/325
387/387
SC (LEV1)
80
100
LEV2
-
-
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.77/0.74 [402/107]
3.11/0.86 [451/125]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
89 [192]
85 [185]
Heat exchanger out-
let (TH3)
44 [111]
44 [111]
Accumulator inlet
7 [45]
7 [45]
Accumulator outlet
7 [45]
7 [45]
SCC outlet (TH6)
22 [72]
24 [75]
Compressor inlet
19 [66]
19 [66]
Compressor shell
bottom
47 [117]
38 [100]
Indoor
unit
LEV inlet
19 [66]
19 [66]
Heat exchanger
outlet
6 [43]
6 [43]
Содержание PUHY-(E)P300
Страница 9: ......
Страница 11: ... 2 ...
Страница 23: ... 14 ...
Страница 25: ... 16 ...
Страница 55: ... 46 ...
Страница 57: ... 48 ...
Страница 67: ... 58 ...
Страница 75: ... 66 ...
Страница 77: ... 68 ...
Страница 80: ... 71 HWE07010 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 73 2 Principal Parts and Functions 74 ...
Страница 81: ... 72 ...
Страница 87: ... 78 ...
Страница 89: ... 80 ...
Страница 113: ... 104 ...
Страница 115: ... 106 ...
Страница 163: ... 154 ...
Страница 255: ... 246 ...
Страница 256: ... 247 HWE07010 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 249 ...
Страница 257: ... 248 ...