Protective functions
Check first when you have a trouble
FR-A800
6 - 39
6.6.2
Motor or machine is making abnormal acoustic noise
Check
points
Possible cause
Countermeasure
Refer to
page
Input
signal
Disturbance due to EMI when frequency or
torque command is given from analog input
(terminal 1, 2, 4).
Take countermeasures against EMI.
Parameter
Setting
Increase the Pr. 74 "Input filter time constant" if
steady operation cannot be performed due to
EMI.
Parameter
Setting
No carrier frequency noises (metallic noises)
are generated.
In the initial setting, Pr. 240 "Soft-PWM
operation selection" is enabled to change
motor noise to an unoffending complex tone.
Therefore, no carrier frequency noises (metallic
noises) are generated.
Set Pr. 240 = "0" to disable this function.
The motor noise increases due to activation
of the carrier frequency automatic
reduction function when the motor is
driven overloaded.
Reduce the load.
Disable the automatic reduction function by
setting Pr. 260 "PWM frequency automatic
switchover" = "0".
Resonance occurs. (output frequency)
Set Pr. 31 to Pr. 36, Pr. 552 (Frequency jump).
When it is desired to avoid resonance
attributable to the natural frequency of a
mechanical system, these parameters allow
resonant frequencies to be jumped.
Resonance occurs. (carrier frequency)
Change Pr. 72 "PWM frequency selection"
setting.
Changing the PWM carrier frequency produces
an effect on avoiding the resonance frequency
of a mechanical system or a motor.
Set a notch filter.
Auto tuning is not performed under
Advanced magnetic flux vector control, Real
sensorless vector control, or vector control.
Perform offline auto tuning.
Gain adjustment during PID control is
insufficient.
To stabilize the measured value, change the
proportional band (Pr. 129) to a larger value, the
integral time (Pr. 130) to a slightly longer time,
and the differential time (Pr. 134) to a slightly
shorter time.
Check the calibration of set point and measured
value.
The gain is too high under Real sensorless
vector control, vector control, or PM
sensorless vector control.
During speed control, check the setting of
Pr. 820 "Speed control P gain 1".
During torque control, check the setting of
Pr. 824 "Torque control P gain 1".
Others
Mechanical looseness
Adjust machine/equipment so that there is no
mechanical looseness.
⎯
Contact the motor manufacturer.
Motor
Operating with output phase loss
Check the motor wiring.
⎯
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......