Parameters
(D) Operation command and frequency command
FR-A800
5 - 273
Selecting the operation mode for power-ON (Pr. 340)
Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power-ON (reset) changes as de-
scribed below.
Use Pr. 340 = "2 or 12" setting to perform communication with the RS-485 terminals.
Even if an instantaneous power failure occurs while Pr. 57 "Restart coasting time" ≠ "9999" (with
automatic restart after instantaneous power failure), inverter continues operation at the condition
before the instantaneous failure.
The operation mode cannot be directly changed between the PU operation mode and Network
operation mode.
Switching between the PU and NET operation modes is available with the PU/EXT key on the
operation panel and the X65 signal.
Pr. 340
setting
Pr. 79
setting
Operation mode at power-ON,
at power restoration, or after a reset
Operation mode switching
0
(initial
value)
0
(initial
value)
External operation mode
Switching among the External, PU, and NET
operation modes is enabled.
1
PU operation mode
PU operation mode fixed
2
External operation mode
Switching between the External and NET operation
modes is enabled.
Switching to PU operation mode is disabled
3, 4
External/PU combined operation mode
Operation mode switching is disabled
6
External operation mode
Switching among the External, PU, and NET
operation mode is enabled while running.
7
X12 (MRS) signal ONExternal operation mode
Switching among the External, PU, and NET
operation modes is enabled.
X12 (MRS) signal OFF External operation mode
External operation mode fixed. (Forcibly switched
to External operation mode.)
1, 2
0
NET operation mode
Same as Pr. 340 ="0" setting
1
PU operation mode
2
NET operation mode
3, 4
External/PU combined operation mode
6
NET operation mode
7
X12(MRS) signal ON NET operation mode
X12 (MRS) signal OFF External operation mode
10, 12
0
NET operation mode
Switching between the PU and NET operation
mode is enabled
1
PU operation mode
Same as Pr. 340 = "0" setting
2
NET operation mode
NET operation mode fixed
3, 4
External/PU combined operation mode
Same as Pr. 340 = "0" setting
6
NET operation mode
Switching between the PU and NET operation
mode is enabled while running.
7
External operation mode
Same as Pr. 340 = "0" setting
Tab. 5-107:
Operation mode of the inverter at power on
Parameters referred to
Pr. 57
Restart coasting time
=>
Pr. 79
Operation mode selection
=>
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......