(A) Application parameters
Parameters
5 - 566
I002713E
Fig. 5-283:
Automatic restart in different operation modes
NOTES
The rotation speed detection time (frequency search) changes according to the rotation speed of
the motor. (maximum 1 s)
When the inverter capacity is two ranks or greater than the motor capacity, the overcurrent pro-
tective function (E.OC[]) is sometimes activated and prevents the inverter from restarting.
If two or more motors are connected to one inverter, this function operates abnormally. (The
inverter does not restart successfully.)
Because a DC injection brake is applied instantaneously at speed detection during a restart, the
speed might drop if the moment of inertia (J) of the load is small.
If reverse operation is detected when "1" (reverse rotation disabled) is set to Pr. 78, operation
decelerates by reverse rotation and then changes to forward rotation when the start command is
forward rotation. The inverter does not restart when the start command is reverse rotation.
When "3, 13" is set to Pr. 162, limit the wiring length to within 100 m.
+
∗
+
∗
V/F control, Advanced magnetic flux vector control
Instantaneous (power failure) time
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E(V)
Coasting
time (Pr. 57)
Speed
detection
time
Restart cushion
time (Pr. 58 setting)
Acceleration time
at a restart
(Pr. 611 setting)
* The output shut off timing differs
according to the load condition.
* The output shut off timing differs
according to the load condition.
Speed
detection
time
Coasting
time (Pr. 57)
Acceleration time
at a restart
(Pr. 611 setting)
Power supply
(R/L1, S/L2,
T/L3)
Motor speed N
(r/min)
Inverter output
frequency f(Hz)
output voltage
E(V)
Instantaneous (power failure) time
Real sensorless vector control
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......