Parameters
(H) Protective function parameter
FR-A800
5 - 301
Overheat protection to match the characteristic of the motor
(Pr. 600 to Pr. 604, Pr. 692 to Pr. 696)
●
The activation level of the electronic thermal O/L relay can be varied to match the motor
temperature characteristic.
●
The electronic thermal O/L relay's activation level can be set using the combination of three points
(Pr. 600, Pr. 601), (Pr. 602, Pr. 603), (Pr. 604, Pr. 9). Two or more points are required for setting.
●
The electronic thermal O/L relay's activation level can be set to using the combination of three
points (Pr. 692, Pr. 693), (Pr. 694, Pr. 695), (Pr. 696, Pr. 51) when the RT signal is ON.
●
When setting Pr. 600, Pr. 602, Pr. 604 (Pr. 692, Pr. 694, Pr. 696) to the same frequency, the following
graph's upper level will be applied.
I002833E
Fig. 5-131:
Setting examples
Fig. 5-132:
Overheat protection setting
I002586E
Fig. 5-133:
Overheat protection setting example
I002587E
NOTE
Make sure to set the parameters according to the motor temperature characteristic used.
Parameters referred to
Pr. 71
Applied motor
=>
Pr. 72
PWM frequency selection
=>
Pr. 178 to Pr. 189
(input terminal function selection)
=>
Pr. 190 to Pr. 196
(output terminal function selection)
=>
Load ratio
Load ratio
Frequency
Setting
example 1
Setting
example 2
Pr. 9 = 100% of the rated
motor current
Pr. 600 = 6 Hz
Pr. 601 = 50 %
Pr. 602 = 30 Hz
Pr. 603 = 70 %
Pr. 604 = 60 Hz
Pr. 600 = 120 Hz
Pr. 601 = 800 %
Pr. 602 = 3 Hz
Pr. 603 = 50 %
Frequency [
Pr. 604 = 80 Hz
100%
Continuous operation characteristic
Load ratio (ratio to Pr. 9 (Pr. 51)) [%]
Output
frequency
Pr. 603
(Pr. 695)
Pr. 601
(Pr. 693)
Pr. 600
(Pr. 692)
Pr. 602
(Pr. 694)
Pr. 604
(Pr. 696)
100
80
50
10
Load ratio [%]
Output frequency [Hz]
Pr. 600 = 10 Hz
Pr. 601 = 80 %
Pr. 602 = 10 Hz
Pr. 603 = 50 %
Pr. 604 = 10 Hz
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......