Parameters
(T) Multi-Function Input Terminal Parameters
FR-A800
5 - 405
●
There are three methods to adjust the frequency setting voltage (current) bias/gain.
( Adjust any point with application of a voltage (current) between terminals 2 and 5 (4 and 5).
Refer to page 5-406.
( Adjust any point without application of a voltage (current) between terminals 2 and 5 (4 and
5). Refer to page 5-407.
( Adjust frequency only without adjustment of voltage (current). Refer to page 5-408.
Analog input display unit changing (Pr. 241)
●
The analog input display unit (%/V/mA) for analog input bias and gain calibration can be changed.
●
Depending on the terminal input specification set to Pr. 73, Pr. 267, and voltage/current input
switches, the display unit of C3 (Pr. 902), C4 (Pr. 903), C6 (Pr. 904), and C7 (Pr. 905) change as
described below:
NOTES
Performing terminal 2 calibration that includes a change of the setting frequency incline changes
terminal 1 setting.
Calibration with voltage input to terminal 1 sets (terminal 2 (4) analog value + terminal 1 analog
value) as the analog calibration value.
Always calibrate the input after changing the voltage/current input signal with Pr. 73, Pr. 267, and
the voltage/current input selection switch.
Analog command (terminals 2, 4)
(depending on Pr. 73, Pr. 267, and
voltage/current input switch)
Pr. 241 = 0 (initial value)
Pr. 241 = 1
0 to 5 V input
0 to 5 V
➔
0 to 100% (0.1%)
0 to 100%
➔
0 to 5 V (0.01 V)
0 to 10 V input
0 to 10 V
➔
0 to 100% (0.1%)
0 to 100%
➔
0 to 5 V (0.01 V) display
0 to 20 mA input
0 to 20 mA
➔
0 to 100% (0.1%)
0 to 100%
➔
0 to 20 mA (0.01 mA)
Tab. 5-156:
Units when displaying the set value
NOTE
When the terminal 1 input specification (0 to ±5 V, 0 to ±10 V) does not agree with the main speed
(terminal 2, terminal 4 input) specification (0 to 5 V, 0 to 10 V, 0 to 20 mA), and if the voltages are
applied to terminal 1, the analog input is not correctly displayed. (For example, in the initial status,
when 0 V is applied to terminal 2 and 10 V is applied to terminal 1, and the analog value is dis-
played as 5 V (100%).)
Use the inverter with the Pr. 241 = "0 (initial value)" setting. (0% display).
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......