Parameters
(G) Control parameters
FR-A800
5 - 663
5.16.7
DC injection brake, zero speed control, and servo lock
●
Timing to stop or braking torque can be adjusted by applying DC injection brake at the time of
stopping motor.
●
Zero speed control can also be selected at the time of the Real sensorless vector control, and zero
speed control and servo lock can be selected at the time of vector control or PM sensorless vector
control.
●
DC injection brake is preventing the motor shaft to turn by applying DC voltage to the motor, and
the other hand, zero speed control is using vector control to maintain 0 r/min. Either way, the
motor shaft will not return to its original position when it is rotated due to external force.
●
Servo lock will maintain the position of the motor shaft. When a motor shaft is rotated by external
force, it goes back to the original position.
●
Select the magnetic flux decay output shutoff function to decay the magnetic flux before shutting
off the output at a stop.
Initial value for the FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower.
Initial values for the FR-A820-00630(11K) to FR-A820-03160(55K), FR-A840-00310(11K) to FR-A840-
01800(55K).
Initial value for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
Pr.
Name
Initial value
Setting
range
Description
10
G100
DC injection brake
operation frequency
3 Hz
0 to 120 Hz
Set the operation frequency for the DC injection
brake (zero speed control and servo lock).
9999
Operate at Pr. 13 or lower
11
G101
DC injection brake
operation time
0.5 s
0
Without DC injection brake (zero speed control and
servo lock)
0.1 to 10 s
Set the operation time for the DC injection brake (zero
speed control and servo lock).
8888
Operate with X13 signal ON
12
G110
DC injection brake
operation voltage
0 to 30%
Set the DC injection brake voltage (torque). When set
to "0", there will be without DC injection brake.
802
G102
Pre-excitation selection
0
0
Zero speed control
1
Servo lock
1299
G108
Second pre-excitation
selection
0
0
Zero speed control
The pre-excitation
operation of the second
Servo lock motor can be
selected.
1
Servo lock
850
G103
Brake operation selection
0
0
DC injection brake operation
1
Zero speed control (Real sensorless vector control)
2
Magnetic flux decay output shutoff (Real sensorless
vector control)
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......