Parameters
(E) Environment setting parameters
FR-A800
5 - 227
5.7.19
Maintenance timer alarm
The maintenance timer output signal (Y95) is output when the inverter's cumulative energization
time reaches the time period set with the parameter. MT1, MT2 or MT3 is displayed on the operation
panel.
This can be used as a guideline for the maintenance time of peripheral devices.
●
The cumulative energization time of the inverter is stored in the EEPROM every hour and displayed
in Pr. 503 (Pr. 686, Pr. 688) in 100 h increments. Pr. 503 (Pr. 686, Pr. 688) is clamped at 9998 (999800 h).
●
When the value in Pr. 503 (Pr. 686, Pr. 688) reaches the time (100 h increments) set in Pr. 504 (Pr. 687,
Pr. 689), Maintenance timer signal (Y95) is output, and also
(MT1),
(MT2), or
(MT3) is displayed on the operation panel.
●
For the terminal used for Y95 signal output, assign the function by setting "95 (positive logic)" or
"195 (negative logic)" in any of Pr. 190 to Pr. 196 (output terminal function selection).
Pr.
Name
Initial value
Setting range
Description
503
E710
Maintenance timer 1
0
0 (1 to 9998)
Displays the inverter's cumulative
energization time in increments of
100 h (read-only).
Writing the setting of "0" clears the
cumulative energization time while
Pr. 503 = "1 to 9998". (Writing is
disabled when Pr. 503 = "0".)
504
E711
Maintenance timer 1 warning
output set time
9999
0 to 9998
Set the time until the maintenance
timer signal (Y95) is output.
MT1 is displayed on the operation
panel.
9999
No function
686
E712
Maintenance timer 2
0
0 (1 to 9998)
The same function as Pr. 503.
687
E713
Maintenance timer 2 warning
output set time
9999
0 to 9998
The same function as Pr. 504.
MT2 is displayed on the operation
panel.
9999
688
E714
Maintenance timer 3
0
0 (1 to 9998)
The same function as Pr. 503.
689
E715
Maintenance timer 3 warning
output set time
9999
0 to 9998
The same function as Pr. 504.
MT3 is displayed on the operation
panel.
9999
I001263E
Fig. 5-79:
Maintenance timer
First power
9998
(999800 h)
Maintenance timer 1
(Pr. 503)
Pr. 504
Y95 signal
(MT1 display)
Set "0" in Pr. 503
OFF
ON
ON
ON
Time
OFF
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......