(E) Environment setting parameters
Parameters
5 - 220
Changing the PWM carrier frequency (Pr. 72)
●
The PWM carrier frequency of the inverter can be changed.
●
Changing the PWM carrier frequency can be effective for avoiding the resonance frequency of
the mechanical system or motor, as a countermeasure against EMI generated from the inverter,
or for reducing leakage current caused by PWM switching.
●
Under Real sensorless vector control, vector control, and PM sensorless vector control, the follow-
ing carrier frequencies are used. (For the control method and fast-response mode selection, refer
to Pr. 800 "Control method selection" page 5-56.)
When low-speed range high-torque characteristic is disabled (Pr. 788 = "0"), 2 kHz is used.
In the low-speed range (3 Hz or lower) under Real sensorless vector control, the carrier frequency
is automatically changed to 2 kHz.
(For FR-A820-00490(7.5K) or lower and FR-A840-00250(7.5K) or lower)
●
When using the optional sine wave filter (MT-BSL/BSC), set Pr. 72 = "25" (2.5 kHz).
(FR-A820-03800(75K) or higher, FR-A840-02160(75K) or higher.)
Soft-PWM control (Pr. 240)
●
Soft-PWM control is a control method that changes the motor noise from a metallic sound into
an inoffensive, complex tone.
●
Setting Pr. 240 = "1" will enable the Soft-PWM control.
●
To enable the Soft-PWM control for the FR-A820-03160(55K) or lower and FR-A840-01800(55K) or
lower, set Pr. 72 to "5 kHz or less".
To enable it for the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher, set Pr. 72 to
"4 kHz or less".
Pr. 72 setting
Carrier frequency (kHz)
Real sensorless vector control,
vector control
PM sensorless vector control
Fast-response mode
0 to 5
2
4
6 to 9
6
10 to 13
10
14, 15
14
Tab. 5-88:
Carrier frequencies in different control modes
NOTES
In the low-speed range (about 10 Hz or lower), the carrier frequency may be automatically low-
ered. Motor noise increases, but not to the point of failure.
When Pr. 72 = "25", the following limitations apply.
●
V/F control is forcibly set.
●
Soft-PWM control is disabled.
●
The maximum output frequency is 60 Hz.
NOTE
While a sine wave filter (Pr. 72 = "25") is being used, the Soft-PWM control is disabled.
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......