(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Parameters
5 - 248
Acceleration/deceleration operation
●
When the acceleration signal (RH) is turned ON, the set frequency increases. The increased speed
at this time is determined by the setting of Pr. 44 "Second acceleration/deceleration time". Turning
OFF the RH signal will stop increasing the set frequency and run the motor at the frequency at
that time.
●
When the deceleration signal (RM) is turned ON, the set frequency decreases. The decreased speed
at this time is determined by the setting of Pr. 45 "Second deceleration time". When Pr. 45 = "9999",
the deceleration speed is the same as Pr. 44 setting. Turning OFF the RM signal will stop decreasing
the set frequency and runs the motor at the frequency at that time.
●
When Pr. 59 = any of "11, 12 or 13", deceleration can be performed to a frequency equal to or lower
than the main speed (External operation mode frequency except multi-speed or PU operation
mode frequency).
I002563E
Fig. 5-100:
Example of the remote setting function
I002564E
Fig. 5-101:
Acceleration/deceleration operation
NOTE
While the RT signal is OFF, Pr. 44 "Second acceleration/deceleration time" and Pr. 45 "Second
deceleration time" are used as the set frequency accelerating/decelerating time at turn ON of the
acceleration/deceleration signal. If the Pr. 7 and Pr. 8 settings are longer, the acceleration/deceler-
ation time set by Pr. 7 and Pr. 8 are applied.
While the RT signal is ON, Pr. 44 and Pr. 45 settings are used as the acceleration/deceleration time
regardless of the Pr. 7 and Pr. 8 settings.
0
0Hz
∗1
Ou
tput fr
equen
cy
(H
Z
)
Set frequency
*1
Acceleration (RH)
Deceleration (RM)
Clear (RL)
Forward rotation (STF)
Power supply
*1 External operation frequency (other than multi-speed) or PU running frequency
ON
When Pr. 59 = "1, 2, 11, 12"
When Pr. 59 = "1, 11"
When Pr. 59 = "3, 13"
When Pr. 59 = "2, 3, 12, 13"
Time
0 Hz
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
0
Output fr
equ
e
nc
y
(HZ)
Main speed
Minimum
frequency
Forward rotation (STF)
Acceleration (RH)
Deceleration (RM)
Pr. 59 = “1, 2, 3”
Decelerates to the main speed
Time
Decelerates to the minimum frequency
Pr. 59 = “ 11, 12, 13”
ON
ON
ON
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......