Parameters
(C) Motor constant parameters
FR-A800
5 - 465
5.13.4
Online auto tuning
If online auto tuning is selected under Advanced magnetic flux vector control, Real sensorless vector
control or vector control, favorable torque accuracy is retained by adjusting temperature even when
the resistance value varies due to increase in the motor temperature.
Performing online auto tuning at startup (setting value "1")
●
By promptly tuning the motor status at startup, accurate operation without being affected by
motor temperature is achieved. Also high torque can be provided at very low speed and stable
operation is possible.
●
When using Advanced magnetic flux vector control (Pr. 80 "Motor capacity," Pr. 81 "Number of
motor poles" or Real sensorless vector control (Pr. 80, Pr. 81, Pr. 800 "Control method selection"),
select the online auto tuning at start.
●
Make sure to perform offline auto tuning before performing online auto tuning.
●
Operation method
Perform offline auto tuning. (Refer to page 5-67.)
Check that Pr. 96 "Auto tuning setting/status" = "3 or 103 (offline auto tuning completion)".
Set Pr. 95 "Online auto tuning selection" = "1 (online auto tuning at start)".
#
Check that the following parameters are set before starting operation.
If a motor with substantially low rated current compared with the rated inverter current is used,
speed and torque accuracies may deteriorate due to torque ripples, etc. Set the rated motor
current to about 40% or higher of the rated inverter current.
,
In the PU operation mode, press FWD/REV key on the operation panel.
For External operation, turn ON the start command (STF signal or STR signal).
Pr.
Name
Initial value
Setting range
Description
95
C111
Online auto tuning
selection
0
0
Do not perform online auto tuning
1
Perform online auto tuning at startup
2
Magnetic flux observer (tuning always)
574
C211
Second motor online
auto tuning
0
0 to 2
Select online auto tuning for the second
motor. (same as Pr. 95)
Pr.
Description
9
Uses both rated motor current and electronic thermal O/L relay.
71
Applicable motor
80
Motor capacity (with the rated motor current equal to or lower than the rated inverter
current)
81
Number of motor poles
Tab. 5-196:
Related Parameters
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
Vector
Vector
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......