Parameters
(C) Motor constant parameters
FR-A800
5 - 451
●
Set a given value as the motor constant parameter. The displayed increments of the read motor
constants can be changed with Pr. 684 "Tuning data unit switchover".
For the FR-A820-03160(55K) lower and FR-A840-01800(55K) or lower.
For the FR-A820-03800(75K) or higher and FR-A840-02160(75K) or higher.
First
motor
Pr.
Second
motor
Pr.
Name
Pr. 684 = 0 (initial value)
Pr. 684 = 1
Initial
value
Setting range
Setting
increments
Range indication
Unit
indication
82
455
Motor excitation
current
0 to ***, 9999
1
0 to 500 A, 9999
0.01 A
9999
0 to 3600 A, 9999
0.1 A
90
458
Motor constant (R1)
0 to 50 Ω, 9999
0.001 Ω
91
459
Motor constant (R2)
0 to 50 Ω, 9999
0.001 Ω
92
460
Motor constant (L1)/
d-shaft inductance
(Ld)
0 to 6000 mH, 9999
0.1 mH
0 to 400 mH, 9999
0.01 mH
93
461
Motor constant (L2)/
q-shaft inductance
(Lq)
0 to 6000 mH, 9999
0.1 mH
0 to 400 mH, 9999
0.01 mH
94
462
Motor constant (X)
0 to 100%, 9999
0.01%
859
860
Torque current/
Rated PM motor
current
0 to 500 A, 9999
0.01 A
0 to 3600 A, 9999
0.1 A
298
560
Frequency search
gain
0 to 32767, 9999
1
0 to 32767, 9999
1
Tab. 5-183:
Parameter setting ranges
NOTES
As the motor constants measured in the offline auto tuning have been converted into internal
data (****), refer to the following setting example when making setting:
Setting example:
To slightly increase the Pr. 90 value (5%)
If Pr. 90 = "2516" is displayed, the value is calculated with 2516 × 1.05 = 2641.8.
Therefore set Pr. 90 = "2642".
(The value displayed has been converted into a value for internal use. Hence, simple addition of a
given value to the displayed value has no significance.)
If "9999" is set, tuning data will be invalid and the constant values for Mitsubishi motors (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA and SF-V5RU (1500 r/min series) and so on) are used.
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......