(D) Operation command and frequency command
Parameters
5 - 272
5.9.2
Startup in Network operation mode at power-ON
When power is switched ON or when power comes back ON after an instantaneous power failure, the
inverter can be started up in the Network operation mode. After the inverter starts up in the Network
operation mode, parameter writing and operation can be commanded from programs.
Set this mode when performing communication operation using the RS-485 terminals or a commu-
nication option.
NOTES
The priority of Pr. 79 and Pr. 340 and signals is Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340.
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 15
Jog frequency
=>
Pr. 4 to Pr. 6, Pr. 24 to 27,
Pr. 232 to Pr. 239
(multi-speed operation)
=>
Pr. 75
Reset selection/disconnected PU detection/PU stop selection
=>
Pr. 161
Frequency setting/key lock operation selection
=>
Pr. 178 to Pr. 182
(input terminal function selection)
=>
Pr. 190 to Pr. 196
(output terminal function selection)
=>
Pr. 340
Communication startup mode selection
=>
Pr. 550
NET mode operation command source selection
=>
Pr.
Name
Initial
value
Setting
range
Description
79
D000
Operation mode selection
0
0 to 4, 6, 7
Selects the operation mode.
(Refer to page 5-263.)
340
D001
Communication startup mode
selection
0
0
Follows the Pr. 79 setting.
1,2
The inverter starts up in the Network operation
mode.
If an instantaneous power failure occurs when
"2" is set, the operating status before the
instantaneous power failure is maintained.
10,12
The inverter starts up in the Network operation
mode. The operation mode can be changed
between the PU operation mode and Network
operation mode from the operation panel.
If an instantaneous power failure occurs when
"12" is set, running is continued at the
condition before the instantaneous power
failure.
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......