(M) Monitor display and monitor output signal
Parameters
5 - 380
5.11.10 Remote
output
function
The inverter output signals can be turned ON/OFF like the remote output terminals of a programma-
ble controller.
Remote output setting (REM signal, Pr. 496, Pr. 497)
●
The output terminal can be turned ON/OFF with the Pr. 496 and Pr. 497 settings. ON/OFF control
can be performed for the remote output terminal via the PU connector, RS-485 terminals and
communication option.
●
To assign the Remote output (REM) signal to the terminal to be used for remote output, set "96
(positive logic) or 196 (negative logic)" in any of Pr. 190 to Pr. 196 (output terminal function
selection).
●
Refer to the fig. 5-178, and set "1" in the terminal bit (terminal with the REM signal assigned) of Pr.
496 or Pr. 497 to turn ON the output terminal (OFF when using negative logic). Set "0" to turn OFF
the output terminal (ON when using negative logic).
●
For example, when Pr. 190 "RUN terminal function selection" = "96" (positive logic) and "1" (H01)
is set in Pr. 496, the terminal RUN turns ON.
Any value.
Y0 to Y6 are available when the extension output option (FR-A8AY) is installed.
RA1 to RA3 are available hen the relay output option (FR-A8AR) is installed.
Pr.
Name
Initial
value
Setting
range
Description
495
M500
Remote output
selection
0
0
Remote output data is cleared
when the power supply is turned
OFF
Remote output data is
cleared during an
inverter reset
1
Remote output data is retained
when the power supply is turned
OFF
10
Remote output data is cleared
when the power supply is turned
OFF
Remote output data is
retained during an
inverter reset
11
Remote output data is retained
when the power supply is turned
OFF
496
M501
Remote output data 1
0
0 to 4095
Set values for the bits corresponding to each output terminal
of the inverter output terminal. (Refer to the diagram below.)
497
M502
Remote output data 2
0
0 to 4095
Set values for the bits corresponding to each output terminal
of options FR-A8AY and FR-A8AR. (Refer to the diagram
below.)
I001157E
Fig. 5-178:
Remote output data
Pr. 496
Pr. 497
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......