Precautions for use of the inverter
Power supply harmonics
FR-A800
3 - 15
●
Determining if a countermeasure is required
A countermeasure for harmonics is required if the following condition is satisfied:
Outgoing harmonic current > maximum value per 1 kW contract power × contract power
●
Harmonic suppression techniques
No. Item
Description
Reactor installation
(FR-HAL, FR-HEL)
Install an AC reactor (FR-HAL) on the AC side of the inverter or a DC reactor (FR-HEL) on its DC
side, or install both to suppress outgoing harmonic currents.
High power factor
converter (FR-HC2)
This converter trims the current waveform to be a sine waveform by switching the rectifier
circuit (converter module) with transistors. Doing so suppresses the generated harmonic
amount significantly. Connect it to the DC area of an inverter. Use the high power factor
converter (FR-HC2) with the accessories that come as standard.
Installation of power
factor improving
capacitor
When used with a reactor connected in series, the power factor improving correction
capacitor can absorb harmonic currents.
Transformer multi-
phase operation
Use two transformers with a phase angle difference of 30° as in
-
Δ
and
Δ
-
Δ
combinations
to provide an effect corresponding to 12 pulses, reducing low-degree harmonic currents.
Passive filter
(AC filter)
A capacitor and a reactor are used together to reduce impedances at specific frequencies.
Harmonic currents are expected to be absorbed greatly by using this technique.
Active filter
This filter detects the current in a circuit generating a harmonic current and generates a
harmonic current equivalent to a difference between that current and a fundamental wave
current to suppress the harmonic current at the detection point. Harmonic currents are
expected to be absorbed greatly by using this technique.
Tab. 3-12:
Suppression of harmonics
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......