(M) Monitor display and monitor output signal
Parameters
5 - 360
●
The estimated value of the consumed power during commercial power supply operation [kW] is
calculated from the motor capacity set in Pr. 893 and Pr. 892 "Load factor" with the following
formula.
Annual power saving amount and power cost savings (Pr. 899)
●
When the operation time rate [%] (ratio of time in year that the inverter actually drives the motor)
is set in Pr. 899, the annual energy saving effect can be estimated.
●
When the operation pattern is determined to a certain extent, the estimated value of the annual
power saving amount can be calculated by measuring the power saving in a certain measurement
period.
●
Refer to the following to set the operation time rate.
Estimate the average time of operation per day [h/day].
Calculate the number of operation days per year [days/year].
(Average number of operation days per month × 12 months)
Calculate the annual operation time [h/year] from
and
.
Annual operation time [h/year] = average time [h/day] × number of operation days [days/year]
#
Calculate the operation time rate and set it in Pr. 899.
●
Calculate the annual power saving amount from Pr. 899 "Operation time rate (estimated value)"
and the average power saving monitor.
●
When the power cost per hour is set in Pr. 896 "Power unit cost", the annual power cost savings
can be monitored.
Estimated consumed power during
commercial power supply operation [kW]
= Pr. 893 [kW] ×
Consumed power [%]
×
Pr. 892 [%]
100
100
NOTE
In commercial power supply operation, because the rotations per minute cannot rise higher than
the power supply frequency, if the output frequency rises to Pr. 3 "Base frequency" or higher, it
stays at a constant value.
Operation time rate (%) =
Annual operation time
[
h/year]
× 100 [%]
24
[
h/day] × 365
[
days/year]
Example
쑴
Setting example for operation time rate:
When operation is performed about 21 h per day for an average 16 operation days per month:
Annual operation time = 21 [h/day] × 16 [days/month] × 12 months = 4032 [h/year]
Set 46.03% in Pr. 899.
쑶
Annual power saving amount
[kWh/year]
=
With Pr. 898 = 10 or 9999, average
power saving [kW] during cumulative
× 24 h × 365 days ×
Pr. 899
100
Annual power cost saving = Annual power saving amount [kWh/year] × Pr. 896
NOTE
During regenerative driving, make calculation on the assumption that "power saving = power dur-
ing commercial power supply operation (input power = 0)".
Operation time rate [%] =
4032 [h/year]
× 100 [%] = 46.03%
24 [h/day] × 365 [days/year]
Содержание FR-A800
Страница 2: ......
Страница 4: ......
Страница 22: ...Contents XVIII ...
Страница 30: ...Related manuals Introduction 1 8 ...
Страница 122: ...Connection of stand alone option units Installation and wiring 2 92 ...
Страница 180: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 934: ...Check first when you have a trouble Protective functions 6 46 ...
Страница 954: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1030: ...EC Declarations of Conformity Appendix A 46 A 5 EC Declarations of Conformity A 5 1 Low Voltage Directive ...
Страница 1031: ...Appendix EC Declarations of Conformity FR A800 A 47 ...
Страница 1032: ...EC Declarations of Conformity Appendix A 48 ...
Страница 1033: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1034: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1035: ...Appendix EC Declarations of Conformity FR A800 A 51 A 5 2 EMC Directive ...
Страница 1036: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1037: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1038: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1039: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1040: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1041: ......