Chapter 3: Using the Web Interface
92
•
sysLocation - the location of the system
4.
To configure SNMP notifications:
c.
Select the Enable SNMP Notifications checkbox.
d.
Select a notification type -- SNMPv2c Trap, SNMPv2c Inform, SNMPv3 Trap, and SNMPv3 Inform.
e.
Specify the SNMP notification destinations and enter necessary information. For more information, see:
•
(on page 194).
•
Note: Any changes made to the 'SNMP Notifications' section on the SNMP page will update the settings of the System
SNMP Notification Action, and vice versa. See Available Actions (on page 131). To add more than three SNMP
destinations, you can create new SNMP notification actions. See Send an SNMP Notification (on page 141).
5.
You must download the SNMP MIB for your PDU to use with your SNMP manager.
a.
Click the Download MIBs title bar to show the download links.
b.
Click the PDU2-MIB download link. See
(on page 195).
6.
Click Save.
Configuring SMTP Settings
The PDU can be configured to send alerts or event messages to a specific administrator by email. See
(on page 119).
To send emails, you have to configure the SMTP settings and enter an IP address for your SMTP server and a sender's
email address.
If any email messages fail to be sent successfully, the failure event and reason are available in the event log. See
or Clearing the Local Event Log
(on page 166).
To set SMTP server settings:
1.
Choose Device Settings > Network Services > SMTP Server.
2.
Enter the information needed.
Field
Description
IP Address/Host Name
Type the name or IP address of the mail server.