Chapter 3: Using the Web Interface
45
2.
View or edit the following fields in the Reachability Settings section.
Note: All fields are required on this section.
Field
Description
AutoPing Status
Display field showing one of the following component status connections:
•
Monitored
•
Error
•
Unreachable
•
Unrecoverable
IP address/hostname
Enter the IP address or host name of the component you want to monitor.
Number of successful pings to enable feature Enter a value for The number of successful pings required to consider the
monitored component as "Reachable." Valid range is 0 to 200.
Wait time (in seconds) after successful ping
Enter the wait time before sending the next ping if the previous ping
responded successfully. Valid range is 5 to 600 (seconds).
Wait time (in seconds) after unsuccessful ping Enter the wait time before sending the next ping if the previous ping did
not respond. Valid range is 3 to 600 (seconds).
Number of consecutive unsuccessful pings for
failure
Enter the number of consecutive pings without any response before the
monitored component is considered "Unreachable." Valid range is 1 to
100.
Wait time (in seconds) before resuming pinging
after failure
Enter the wait time before the PDU resumes pinging after the monitored
equipment is considered "Unreachable." Valid range is 1 to 1200
(seconds).
3.
View or edit the following fields in the Actions on Failure/Recovery section.
Field
Description
Send EMAIL status for AutoPing monitoring for
this outlet
Select this checkbox to enable email status for AutoPing monitoring of the
component.
Recipient Email Addresses
Enter email addresses (separated by commas) to receive AutoPing
notifications.