Chapter 3: Using the Web Interface
139
a.
If no messaging actions are available, create them now. See
(on page 131).
b.
To select any methods, select them one by one in the Available field.
To add all available methods, simply click Select All.
c.
To delete any methods, click a method's
in the Selected field.
To remove all methods, simply click Deselect All.
8.
In the Available Sensors field, select the desired target's sensor.
a.
Click the first
to select a target sensor from the list.
b.
Click the second
to select the specific sensor for the target from the list.
c.
Click
to add the selected sensor to the Report Sensors list box.
For example, to monitor the current reading of the Inlet 1, select Inlet 1 from the left field, and then select RMS Current
from the right field.
9.
To report additional sensors simultaneously, repeat the above step to add more sensors.