KE300A Inverter Parameter Description
102
P4-28
HDI minimum input
Factory default
0.00kHz
Setting range
0.00kHz ~ P4-30
P4-29
HDI minimum input corresponding setting Factory default
0.0%
Setting range
-100.00% ~ 100.0%
P4-30
HDI maximum input
Factory default
50.00kHz
Setting range
P4-28 ~ 100.00kHz
P4-31
HDI maximum input setting
Factory default
100.0%
Setting range
-100.00% ~ 100.0%
P4-32
HDI filter time
Factory default
0.10s
Setting range
0.00s ~ 10.00s
This group of function code defines the corresponding relationship when the pulse is used as frequency
setting mode.
The pulse frequency input can only be input via HDI channel. The applications of this group function are
similar as those of AI curve 1 function.
P4-33
AI curve selection
Factory default
321
Setting range
Units place
AI1 curve selection
1
Curve 1 (see P4-13 ~ P4-16)
2
Curve 2 (see P4-18 ~ P4-21)
3
Curve 3 (see P4-23 ~ P4-26)
Tens place
AI2 curve selection, ibid
Units place and tens place of this function code are used to select analog input AI1, AI2 corresponding
setting curve.
Curve 1, curve 2, curve 3 are 2 points curves, set by P4 group.
Standard inverter has 2 analog input terminals.
P4-34
AI below minimum input setting selection
Factory default
000
Setting range
Units place
AI1 below minimum input setting selection
0
Correspond to minimum input setting
1
0.0%
Tens place
AI2 below minimum input setting selection
(0 ~ 1, ibid)
Hundreds
place
Keypad potentiometer below minimum input setting
selection (0 ~ 1, ibid)
The parameter is used to set how to confirm the analog corresponding setting when the analog input
voltage is lower than the setting “the minimum input”.
Units place, tens place and hundreds place of this function code correspond to the analog input AI1, AI2
and Keypad potentiometer.
If the selection is 0, when AI input is lower than “the minimum input”, the analog value corresponding
setting is the curve “the minimum input corresponding setting” (P4-14, P4-19, P4-24) determined by the
function code.