KE300A Inverter Parameter Description
157
Group U0 Monitoring Parameters
For the convenience of the field debugging, U0 group indicates running status of inverter. User can view
them on the keypad.
Code
Name
Range
U0-00
Running frequency
0.00
~
320.00Hz(P0-22=2)
0.0
~
3200.0Hz(P0-22=1)
U0-01
Setting frequency
U0-00 displays absolute value of theoretical running frequency of the inverter.
U0-01 displays absolute value of setting frequency of the inverter.
The actual output frequency of inverter refers to U0-19.
Code
Name
Range
U0-02
DC bus voltage
0.0V
~
3000.0V
U0-02 displays the voltage of DC bus.
Code
Name
Range
U0-03
Output voltage
0V
~
1140V
U0-03 displays the output voltage of inverter at run time.
Code
Name
Range
U0-04
Output current
0.00A
~
655.35A( Rated Power
≤
55kW)
0.0A
~
6553.5A(Rated Power
>
55kW)
U0-04 displays the output current of inverter at run time.
Code
Name
Range
U0-05
Output power
0
~
32767
U0-05 displays the output power of inverter at run time.
Code
Name
Range
U0-06
Output torque
-200.0%
~
200.0%
U0-06 displays the output torque of inverter at run time.
Code
Name
Range
U0-07
DI input status
0
~
32767
U0-07 displays the digital value Input terminal state which can be expressed by a 8-bit binary code; if the
inverter detects that the input of corresponding terminal is high level(closed), then this bit is set to "1", if the
input of corresponding terminal is low level(open), then the bit is set to "0". The relationship between Digital
value Input terminal and binary code is shown below.