KE300A Inverter Parameter Description
131
P9-47
Fault protection action selection 1
Factory default
00000
Setting range
Units place
Motor overload (E-11)
0
Coast to stop
1
Dec-to-stop
2
Keep running
Tens place
Input phase failure (E-12) (same as units place)
Hundreds place
Output phase failure (E-13) (same as units place)
Thousands place
External fault (E-14) (same as units place)
Ten thousands place Communication fault (E-15) (same as units place)
P9-48
Fault protection action selection 2
Factory default
00000
Setting range
Units place
Reserved
Tens place
E
2
PROM W/R fault (E-21)
0
Coast to stop
1
Dec-to-stop
Hundreds place
Reserved
Thousands place
Reserved
Ten thousands place
Running time arrival (E-26) (same as units place of
P9-47)
P9-49
Fault protection action selection 3
Factory default
00000
Setting range
Units place
Customized fault 1 (E-27) (same as units place of
P9-47)
Tens place
Customized fault 2 (E-28) (same as units place of
P9-47)
Hundreds place
Power-on time arrival (E-29) (same as P9-487
units place)
Thousands place
Off load (E-30)
0
Coast to stop
1
Dec-to-stop
2
Deceleration to 7% of motor rated power, then
keep running; run at setting frequency when no
off-load
P9-37
The first fault frequency
Same as P9-17 ~ P9-24
P9-38
The first fault current
P9-39
The first fault bus voltage
P9-40
The first fault input terminal status
P9-41
The first fault output terminal status
P9-42
The first fault inverter status
P9-43
The first fault power on time
P9-44
The first fault running time