KE300A Inverter                                                 Product Information 

 

25 

 
2.6.3 Keypad External Dimension 
 

58

76

30.2

5 0 .0 0

 

Keypad dimension of 1AC/3AC 220V 0.4~1.5kW inverters 

 
Illustration:

 This keypad can be connected with the inverter externally by ordinary network cable, also can 

be mounted on the front side of panel directly. The suggested thickness of panel is 1.2mm. 

55.4

73.4

 

The installation size on the panel while using this keypad 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание KE300A Series

Страница 1: ...install the cover or protective guard as specified firstly and operate the products in accordance with the instructions Since the drawings in this manual are represented examples some are subject to...

Страница 2: ...1 Keypad Description 43 4 2 Function Code Checking and Modification Methods Description 45 4 3 Power on Initialization 45 4 4 Fault Protection 45 4 5 Stand By 46 4 6 Running 46 4 7 Password Setting 46...

Страница 3: ...MC Electromagnetic Compatibility 164 7 1 Definition 164 7 2 EMC Standard Description 164 7 3 EMC Guide 164 Chapter 8 Trouble Shooting 167 8 1 Fault and Trouble Shooting 167 8 2 Common Faults and Solut...

Страница 4: ...injury Use the motor with Class B or above insulation Otherwise there may be risk of electric shock Caution Carefully handled when loading otherwise it may damage the inverter Please don t use the dam...

Страница 5: ...oltage class is consistent with the rated voltage of the inverter and whether the I O cable connecting positions are correct and check whether the external circuit is short circuited and whether the c...

Страница 6: ...ator of the inverter is OFF Otherwise the residual charge on the capacitor may cause personal injury The inverter should be repaired and maintained only by the qualified person who has received profes...

Страница 7: ...minal If a contactor is installed between the power supply and the input terminal of the inverter it is not allowed to use the contactor to control the startup stop of the inverter If such contactor i...

Страница 8: ...ptable motors in according to the rated current of the motor In applications where drive permanent magnetic synchronous motor is required please consult our company 2 The cooling fan and the rotor sha...

Страница 9: ...Check with a screw driver if necessary User s manual certification and other spares User s manual and the relative spares Please contact the local agent or our company directly if there is any damage...

Страница 10: ...2 1 5 2 14 7 KE300A 2R2G S2 2 2 3 23 9 6 KE300A 004G S2 4 0 5 40 17 KE300A 5R5G S2 5 5 7 5 60 25 KE300A 7R5G S2 7 5 10 75 32 KE300A 011G S2 11 15 110 45 KE300A 015G S2 15 20 140 60 KE300A 018G S2 18 5...

Страница 11: ...75 214 256 210 253 KE300A 132G 160P T4 132 160 175 210 256 307 253 304 KE300A 160G 185P T4 160 185 210 250 307 350 304 340 KE300A 185G 200P T4 185 200 250 260 350 385 340 377 KE300A 200G 220P T4 200 2...

Страница 12: ...1200 1600 1290 1280 KE300A 1400G T6 1400 1860 1510 1460 KE300A 1600G T6 1600 2130 1780 1720 2 5 Technical Specifications Table 2 2 KE300A Series Inverter Technical Specifications Item Technical Index...

Страница 13: ...ltage fluctuating Control Function Common DC bus Common DC bus for several inverters energy balanced automatically Torque control Torque control without PG Torque limit Rooter characteristics limit th...

Страница 14: ...t temperature 10 40 derated 4 when the temperature rise by every 1 40 50 Humidity 90 RH or less non condensing Altitude 1000M output rated power 1000M output derated Storage temperature 20 60 2 6 Exte...

Страница 15: ...er Product Information 12 Figure 2 3 Parts of inverter Inverter hoisting hole Inverter mounting hole Keypad bracket Control board Main circuit wiring When installing a cabinet can outlet front back le...

Страница 16: ...A Inverter Product Information 13 2 6 2 External Installation Dimensions 1AC 220V output 0 4 11kW inverters dimension 0 4 1 5kW 5 0 0 0 A W B H D 2 2kW 50 00 78 73 73 128 140 M4 Grounding 124 8 121 8...

Страница 17: ...olt Model W H1 H2 D A B 0 4 1 5kW 78 148 4 124 8 73 128 M4 2 2kW 135 240 173 122 6 229 M4 4 0kW 170 285 176 158 273 5 M4 5 5kW 200 329 1 300 177 2 90 316 6 M4 7 5kW 225 397 6 365 185 2 120 384 1 M5 11...

Страница 18: ...KE300A Inverter Product Information 15 5 0 0 0 A W B H D 2 2 4 0kW W H1 D A B H2 5 5 15kW W A H1 B H2 D 18 5 30kW...

Страница 19: ...8 73 128 M4 2 2kW 110 185 153 98 174 M4 4 0kW 135 240 173 122 6 229 M4 5 5kW 170 285 176 158 273 5 M4 7 5kW 200 329 1 300 177 2 90 316 6 M4 11kW 225 397 6 365 185 2 120 384 1 M5 15kW 255 439 6 402 4...

Страница 20: ...110 160kW Power Range External Dimension mm Installation Dimension mm Mounting Bolt Model W H1 H2 D A B 37kW 320 600 552 330 230 582 M8 45 55kW 320 715 662 330 230 695 5 M8 75 90kW 480 790 725 385 36...

Страница 21: ...KE300A Inverter Product Information 18 3AC 380V inverters dimension 5 0 0 0 A W B H D 0 75 5 5kW W H1 D A B H2 7 5 30kW...

Страница 22: ...KE300A Inverter Product Information 19 W A H1 B H2 D 37 200kW including 90 200kW standard inverter without base 5 0 0 0 W H2 H1 D 90 200kW nonstandard inverter with base...

Страница 23: ...316 6 M4 18 5 22kW 225 397 6 365 185 2 120 384 1 M5 30kW 255 439 6 402 4 209 6 140 423 6 M5 37 45kW 280 570 521 2 258 190 552 M6 55 75kW 320 600 552 330 230 582 M8 90 110kW without base 320 715 662 3...

Страница 24: ...Mounting Bolt Model W H1 H2 D A1 A2 B 220 315kW without base 700 970 900 408 200 600 946 M10 220 315kW with base 700 1390 1350 408 350 710kW without base 940 1170 1100 458 280 820 1146 M10 350 710kW...

Страница 25: ...KE300A Inverter Product Information 22 3AC 660V inverters dimension W A H1 B H2 D 15 200kW without base 5 0 0 0 W H2 H1 D 160 200kW base is optional...

Страница 26: ...2 D A B 15 30kW without base 255 547 504 4 208 4 150 530 5 M6 37 132kW without base 320 715 662 330 230 695 5 M8 160 200kW without base 480 790 725 385 360 768 M10 160 200kW with base 480 1165 1125 38...

Страница 27: ...Mounting Bolt Model W H1 H2 D A1 A2 B 220 250kW without base 700 970 900 408 200 600 946 M10 220 250kW with base 700 1390 1350 408 280 800kW without base 940 1170 1100 458 280 820 1146 M10 280 800kW...

Страница 28: ...ion of 1AC 3AC 220V 0 4 1 5kW inverters Illustration This keypad can be connected with the inverter externally by ordinary network cable also can be mounted on the front side of panel directly The sug...

Страница 29: ...ion of other inverters Illustration This keypad can be connected with the inverter externally by ordinary network cable and it needs an additional bracket to fix it 73 3 108 3 16 6 69 5 104 5 65 100mm...

Страница 30: ...3 The oil stain on the inverter cooling fan should be effectively removed 2 7 2 Periodic Inspection Please perform periodic inspection on the places where the inspection is a difficult thing Periodic...

Страница 31: ...storage will degrade the electrolytic capacitor Thus the product should be powered up once every 2 years each time lasting at least five hours The input voltage should be increased slowly to the rated...

Страница 32: ...and should be kept away from such equipment as punching machine 4 The inverter should be mounted in locations free from direct sunlight high humidity and condensate 5 The inverter should be mounted i...

Страница 33: ...recommended to mount the radiator outside the cabinet In this case the space in the sealed cabinet should be large enough 3 2 Electrical Installation 3 2 1 Guide to the external electrical parts Table...

Страница 34: ...125 100 16 10 1 5 KE300A 037G 045P T4 160 100 16 16 1 5 KE300A 045G 055P T4 200 125 25 25 1 5 KE300A 055G 075P T4 200 125 35 25 1 5 KE300A 075G 090P T4 250 160 50 35 1 5 KE300A 090G 110P T4 250 160 70...

Страница 35: ...ll the capacitor or surge suppressor at the output side of the inverter otherwise it may cause inverter failure or capacitor and surge suppressor damaged The Inverter input output main circuit contain...

Страница 36: ...ut side of the inverter Reduce the external conduction and radiation interference of the inverter Decrease the conduction interference flowing from the power end to the inverter and improve the anti i...

Страница 37: ...t 1 Frequency setting GND PE W V U MOTOR GND AO1 0 10V 4 20mA Analog output 1 0 4 1 5kW Inverter T1 C T1 A T1 B Relay output 1 1K 5K 0 10Vinput 4 20mA 485 485 V I Jumper J1 I V Multifunctional On off...

Страница 38: ...2 3 phase 380 15 50 60Hz Instantaneous shortcut protection circuit R S T Multifunctional 0n off input 1 D1 D2 D4 D3 D6 D5 COM PE Power supply for frequency setting AI1 Analog input 1 GND PE W V U MOT...

Страница 39: ...ise there may be danger of electric shock or fire Caution Make sure that the rated value of the input power supply is consistent with that of the inverter Otherwise it may damage the inverter Make sur...

Страница 40: ...ection terminal of brake resistor Connection point of brake resistor of the inverters below 18 5kW 220V the inverters below 37kW other voltages P1 Connection terminal of external DC reactor Connection...

Страница 41: ...output side of the inverter The inverter output side cannot connect to the capacitor or surge absorber Otherwise it may cause frequent inverter protection and even damage the inverter In case the moto...

Страница 42: ...impedance 20k voltage 500 current AI2 GND Analog input terminal 2 1 Input range DC 0V 10V 4mA 20mA determined by J2 jumper on the control board 2 Input impedance 20k voltage 500 current Digital Input...

Страница 43: ...1B T1C Normally closed terminal Driving capacity AC 250V 3A COS 0 4 DC 30V 1A T1A T1C Normally open terminal Relay Output 2 T2B T2C Normally closed terminal Driving capacity AC 250V 3A COS 0 4 DC 30V...

Страница 44: ...adopted necessary filtering measures should be taken to prevent the interference to the power supply It is recommended to use the contact control mode D1 D7 terminal connection NPN type Figure 3 17 N...

Страница 45: ...pe Figure 3 18 PNP type wiring In this type 24V terminal must disconnect with PLC terminal 24V should connect the common port of external controller and meantime short connect PLC and COM External con...

Страница 46: ...rol start and stop Figure4 1 Operation Keypad Diagram 1 Function key description Function indicator Description RUN Extinguished stop status Light on operating status FWD REV Extinguished forward oper...

Страница 47: ...vely enter menu and confirm parameters Increment key Progressively increase of data or function codes Decrement key Progressively decrease of data or function codes Shift key Select the displayed para...

Страница 48: ...z to 15 00Hz The bold type word indicates the flashing bit In level 3 menu if there is no flashing bit it indicates that the function code cannot be modified The possible reasons include 1 The functio...

Страница 49: ...n be switched in sequence by pressing button 4 7 Password Setting The inverter provides user password protection function When PP 00 is set to non zero value it indicates the user password and the pas...

Страница 50: ...without load Finally complete the automatic tuning of motor parameters If the motor cannot be completely disconnected with the load set P1 11 to 1 static tuning and then press RUN key on the keyboard...

Страница 51: ...arameter group U0 is monitor function parameter group If PP 00 is set to non zero value it means parameter protection password is set and the parameter menu cannot be entered until correct password is...

Страница 52: ...UP and DOWN Adjustable recorded 2 Al1 3 Al2 4 Keypad potentiometer 5 High speed pulse HDI 6 Multi step speed 7 Simple PLC 8 PID 9 Communication 1 P0 04 Auxiliary frequency source B selection The same...

Страница 53: ...t offset 0 00Hz P0 10 max frequency 0 00Hz P0 14 Frequency lower limit 0 00Hz P0 12 frequency upper limit 0 00Hz P0 15 Carrier frequency 1 0kHz 16 0kHz Model depend P0 16 Carrier frequency adjusting a...

Страница 54: ...ication Tens place Terminal command combination with frequency source Hundreds place Communication command combination with frequency source 000 P1 Group Motor Parameters P1 00 Motor type 0 Common asy...

Страница 55: ...or paramet er P1 11 Parameters autotuning 0 No action 1 Static autotuning 2 Rotation autotuning 0 P2 Group Vector Control Parameters P2 00 Speed loop proportional gain 1 1 100 30 P2 01 Speed loop inte...

Страница 56: ...4 V F voltage point 1 0 0 100 0 0 0 P3 05 V F frequency point 2 P3 03 P3 07 0 00Hz P3 06 V F voltage point 2 0 0 100 0 0 0 P3 07 V F frequency point 3 P3 05 P1 04 motor rated power 0 00Hz P3 08 V F vo...

Страница 57: ...nning command switching terminal 21 ACC DEC invalid 22 PID Pause 23 PLC status reset 24 Wobble frequency pause 25 Counter input 26 Counter reset 27 Length count input 28 Length reset 29 Torque control...

Страница 58: ...0V P4 16 AI curve 1 maximum input corresponding setting 100 0 100 0 100 0 P4 17 AI1 filter time 0 00s 10 00s 0 10s P4 18 AI curve 2 minimum input 0 00V P4 20 0 00V P4 19 AI curve 2 minimum input corre...

Страница 59: ...00 P4 35 D1 delay time 0 0s 3600 0s 0 0s P4 36 D2 delay time 0 0s 3600 0s 0 0s P4 37 D3 delay time 0 0s 3600 0s 0 0s P4 38 DI terminal valid mode selection 1 0 Active high 1 Active low Units place D1...

Страница 60: ...n finished reserved 22 Orientation approach reserved 23 Zero speed running 2 output when stop 24 Accumulated power on time arrival 25 FDT2 output 26 Frequency 1 arrival output 27 Frequency 2 arrival o...

Страница 61: ...O2 output function selection 0 P5 09 HDO output maximum frequency 0 01kHz 100 00kHz 50 00kH z P5 10 AO1 offset coefficient 100 0 100 0 0 0 P5 11 AO1 gain 10 00 10 00 1 00 P5 12 AO2 offset coefficient...

Страница 62: ...P6 07 ACC DEC mode 0 Linear ACC DEC 1 S curve ACC DEC A 2 S curve ACC DEC B 0 P6 08 Time of S curve s start part 0 0 100 0 P6 09 30 0 P6 09 Time of S curve s end part 0 0 100 0 P6 08 30 0 P6 10 Stop m...

Страница 63: ...age V Bit11 Radiator temperature Bit12 Count value Bit13 Length value Bit14 Load speed display Bit15 PID setting 81F P7 04 Running status display 2 0000 FFFF Bit00 PID feedback Bit01 PLC step Bit02 HD...

Страница 64: ...epend P7 09 Accumulated running time 0h 65535h P7 10 Model No P7 11 Software version No P7 12 Load speed display decimal place 0 0 decimal place 1 1 decimal place 2 2 decimal places 3 3 decimal places...

Страница 65: ...0 00Hz 10 00Hz 0 00Hz P8 16 Reserved P8 17 P8 18 Power on running command valid protection selection 0 No protection 1 Protection 0 P8 19 Frequency detection value FDT1 0 00Hz P0 10 maximum frequency...

Страница 66: ...0 P8 37 Output current over limit detection delay time 0 00s 360 00s 0 00s P8 38 Any arrival current 1 0 0 300 0 motor rated current 100 0 P8 39 Any arrival current 1 amplitude 0 0 300 0 motor rated c...

Страница 67: ...0 0 P9 04 Stall over voltage point Braking threshold 120 150 130 P9 05 Stall over current gain 1 100 20 P9 06 Stall over current point 100 200 160 P9 07 Short circuit to ground protection selection wh...

Страница 68: ...ort circuit to ground fault 24 Reserved 25 Reserved 26 Running time arrival 27 Customized fault 1 28 Customized fault 2 29 Power on time arrival 30 Off load 31 PID feedback lost when running 40 Fast c...

Страница 69: ...fault P9 33 Power on time at the second fault P9 34 Running time at the second fault P9 37 Frequency at the first fault P9 38 Current at the first fault P9 39 Bus voltage at the first fault P9 40 Inp...

Страница 70: ...top 2 Keep running Tens place Customized fault 2 28 0 Coast to stop 1 Dec to stop 2 Keep running Hundreds place Power on time arrival time 29 0 Coast to stop 1 Dec to stop 2 Keep running Thousands pla...

Страница 71: ...Instantaneous power off 80 100 0 90 0 P9 61 Recover judgment time when Instantaneous power off 0 00s 100 00s 0 50s P9 62 Action judgment voltage when instantaneous power off 60 0 100 0 standard bus vo...

Страница 72: ...filter time 0 00 650 00s 0 00s PA 12 PID feedback filter time 0 00 60 00s 0 00s PA 13 PID output filter time 0 00 60 00s 0 00s PA 14 Sampling period 0 00 65535 2 PA 15 Proportional gain Kp2 0 0 100 0...

Страница 73: ...elative to maximum frequency 0 Pb 01 Wobble frequency amplitude 0 0 100 0 0 0 Pb 02 Sudden Jump frequency amplitude 0 0 50 0 0 0 Pb 03 Wobble frequency cycle 0 1s 3000 0s 10 0s Pb 04 Triangular wave r...

Страница 74: ...selection when power down Units place Storage selection when power off 0 Not store 1 Store Tens place Storage selection when stop 0 Not store 1 Store 00 PC 18 0th phase running time 0 0s m 6500 0s m 0...

Страница 75: ...3 0 PC 40 11th phase running time 0 0s m 6500 0s m 0 0s m PC 41 11th phase ACC DCC time selection 0 3 0 PC 42 12th phase running time 0 0s m 6500 0s m 0 0s m PC 43 12th phase ACC DCC time selection 0...

Страница 76: ...0 0 invalid 0 1s 60 0s 0 0 Pd 05 Communication protocol selection 0 Non standard MODBUS protocol 1 Standard MODBUS protocol 1 Pd 06 Communication selection Units place Current resolution 0 0 01A 1 0 1...

Страница 77: ...150 0 A0 04 Torque filter time 0 00s 10 00s 0 00s A0 05 Forward maximum frequency in torque control mode 0 00Hz P0 10 maximum frequency 50 00Hz A0 06 Reverse maximum frequency in torque control mode...

Страница 78: ...mum unit U0 Group Basic Monitoring Parameter U0 00 Running frequency Hz 0 01Hz U0 01 Setting frequency Hz 0 01Hz U0 02 DC bus voltage V 0 1V U0 03 Output voltage V 1V U0 04 Output current A 0 01A U0 0...

Страница 79: ...lue 0 01 U0 29 Reserved 0 01Hz U0 30 Main frequency A display 0 01Hz U0 31 Auxiliary frequency B display 0 01Hz U0 32 Reserved 1 U0 33 Reserved 0 1 U0 34 Motor temperature 1 U0 35 Target torque 0 1 U0...

Страница 80: ...chine tool injection molding machine centrifugal machine and wire drawing machine etc Note The autotuning of motor parameters must be accomplished properly if you use the sensorless vector control How...

Страница 81: ...f multifunctional input terminals Not store means that the setting frequency is recovered to the value of P0 08 in case of inverter power off 1 Keypad store The initial value is the value of P0 08 Sto...

Страница 82: ...entiometer 5 High speed PULSE HDI 6 Multi step speed 7 Simple PLC 8 PID 9 Communication When the auxiliary frequency source is used as independent frequency reference channel i e frequency source swit...

Страница 83: ...hip between frequency A and B 0 A B 1 A B 2 Max A B 3 Min A B Units place Frequency source selection 0 Main frequency source A Reference frequency A 1 Calculation result of frequency A and B Reference...

Страница 84: ...digital setting of the inverter P0 09 Running direction Factory default 0 Setting range 0 Direction is forward 1 Direction is reverse Through modifying this function code it can change the rotary dire...

Страница 85: ...etting range 0 00Hz P0 12 frequency upper limit If the reference frequency is lower than frequency lower limit the inverter can stop or run with lower limit frequency or run at zero speed which is set...

Страница 86: ...Model depend Setting range 0 00s 36000s Acceleration time is the time of accelerating from 0Hz to ACC DEC time reference frequency P0 25 Deceleration time is the time of decelerating from ACC DEC tim...

Страница 87: ...ution is 0 01Hz the MAX output frequency is 300 00Hz Note When modifying this parameter the decimal place of all the parameters related to frequency changes the corresponding frequency value changes t...

Страница 88: ...quency source 0 No combination 1 Keypad setting frequency 2 AI1 3 AI2 4 Keypad potentiometer 5 High speed pulse HDI 6 Multi step speed 7 Simple PLC 8 PID 9 Communication Tens place Terminal command co...

Страница 89: ...rated motor parameters P1 06 Motor stator resistance Factory default Model depend Setting range 0 001 65 535 Inverter power 55kW 0 0001 6 5535 Inverter power 55kW P1 07 Motor rotor resistance Factory...

Страница 90: ...N key the inverter will make static autotuning 2 Motor parameter rotation autotuning To ensure the dynamic control performance of inverter please select rotation autotuning During the rotation autotun...

Страница 91: ...ustment parameters when the running frequency is lower than low switching frequency P2 02 P2 03 and P2 04 are PI adjustment parameters when the running frequency is higher than high switching frequenc...

Страница 92: ...tor is torque current command This parameter is used to filter the torque command This parameter needs no adjustment generally and this filter time can be increased in case of huge speed fluctuation I...

Страница 93: ...que upper limit digital setting Factory default 150 0 Setting range 0 0 200 0 In the speed control mode the maximum of the inverter output torque is controlled by the torque upper limit source P2 09 i...

Страница 94: ...al machine 2 Square V F curve It is suitable for the centrifugal loads such as fan and pump 3 8 VF curve between linear VF and square VF P3 01 Torque boost Factory default Model depend Setting range 0...

Страница 95: ...ory default 0 00Hz Setting range P3 03 P3 07 P3 06 V F voltage point 2 Factory default 0 0 Setting range 0 0 100 0 P3 07 V F frequency point 3 Factory default 0 00Hz Setting range P3 05 P1 04 motor ra...

Страница 96: ...the application which over voltage fault happens frequently during deceleration the over excitation gain needs to be increased But the current would be increased if the over excitation is too bigger...

Страница 97: ...frequency and Jog ACC DEC time please refer to P8 00 P8 01 and P8 02 5 Reverse Jog RJOG 6 Terminal UP When the frequency is given by the external terminals it is used as increment and decrement comman...

Страница 98: ...ID of frequency source 23 PLC status reset PLC pauses during the execution process When it runs again it can restore to the initial status of simple PLC via this terminal 24 Wobble frequency pause The...

Страница 99: ...l mode the inverter switches to another mode when the terminal is valid 47 Emergency stop When the terminal is valid the inverter stops with fastest speed during the process the current is as upper li...

Страница 100: ...ime 1 P0 17 P0 18 OFF ON ACC time DEC time 2 P8 03 P8 04 ON OFF ACC time DEC time 3 P8 05 P8 06 ON ON ACC time DEC time 4 P8 07 P8 08 P4 10 Terminal filter time Factory default 0 010s Setting range 0...

Страница 101: ...igure 6 6 Three line Running Mode 2 2 Three line running mode 1 In this mode DIn is enabled terminal and the direction is controlled by FWD and REV respectively However the pulse is enabled through di...

Страница 102: ...x 1 Forward running FWD DIy 2 Reverse running REV DIn 3 Three line running control To make the inverter run users must close DIn terminal firstly and then the motor running signal will be generated by...

Страница 103: ...analog input setting value When the analog input voltage is bigger than P4 15 maximum input of AI curve 1 then calculate the analog voltage according to maximum input When the analog input voltage is...

Страница 104: ...10 00V P4 21 AI curve 2 maximum input corresponding setting Factory default 100 0 Setting range 100 00 100 0 P4 22 AI2 filter time Factory default 0 10s Setting range 0 00s 10 00s P4 23 AI curve 3 min...

Страница 105: ...ens place AI2 curve selection ibid Units place and tens place of this function code are used to select analog input AI1 AI2 corresponding setting curve Curve 1 curve 2 curve 3 are 2 points curves set...

Страница 106: ...ace DI1 terminal valid status setting 0 Active high 1 Active low Tens place D2 terminal valid status setting 0 1 ibid Hundreds place D3 terminal valid status setting 0 1 ibid Thousands place D4 termin...

Страница 107: ...ls 4 Frequency arrival Please refer to P8 21 for details 5 Zero speed running no output when stop When the inverter is running the output frequency is 0 it outputs ON signal When the inverter stopped...

Страница 108: ...se refer to P8 28 P8 29 description 26 Frequency 1 arrival output Please refer to P8 30 P8 31 description 27 Frequency 2 arrival output Please refer to P8 32 P8 33 description 28 Current 1 arrival out...

Страница 109: ...unction Range 0 Running frequency 0 maximum output frequency 1 Setting frequency 0 maximum output frequency 2 Output current 0 2 times motor rated current 3 Output torque 0 2 times motor rated torque...

Страница 110: ...9 09 A9 10 need to be selected no need to set the zero offset coefficient The analog output deviation is corrected by the corresponding P5 11 and P5 13 gains P5 17 HDO open collector output delay time...

Страница 111: ...urately Group P1 2 pre excitation start Only valid for asynchronous motor used to establish magnetic field before motor running For pre excitation current pre excitation time please refer to P6 05 P6...

Страница 112: ...2 0s At this time the inverter accelerates to 5Hz and further to the reference frequency 10Hz in 2s P6 05 DC braking current before start pre excitation current Factory default 0 Setting range 0 100...

Страница 113: ...uency needs fast ACC DEC When setting frequency is above rated frequency ACC DEC time is f is setting frequency fb is motor rated frequency T is the ACC time from 0Hz to rated frequency P6 08 Time of...

Страница 114: ...y P6 12 DC braking waiting time after stop Factory default 0 0s Setting range 0 0s 100 0s P6 13 DC braking current after stop Factory default 0 Setting range 0 100 P6 14 DC braking time after stop Fac...

Страница 115: ...put voltage Dc braking current after stop Dc braking start frequency after stop Output frequency Hz Time t Time t Figure 6 12 DC braking diagram P6 15 Braking usage ratio Factory default 100 Setting r...

Страница 116: ...key whose function can be defined by the value 0 This key is invalid 1 Switching between keyboard command and remote operation It refers to switching of command source switching between the current co...

Страница 117: ...voltage V Output current A Output power kW Output torque DI input status 15 14 13 12 11 10 9 8 DO output status AI1 voltage V AI2 voltage V Radiator temperature Count value Length value Load speed dis...

Страница 118: ...ime Min HDO frequency kHz Communication setting value Reserved Main frequency Adisplay Hz Auxiliary frequency B display Hz If the above parameters need to be displayed when running set the correspondi...

Страница 119: ...tatus DO output status AI1 voltage V AI2 voltage V Radiator temperature Count value 15 14 13 12 11 10 9 8 Length value PLC phase Load speed PID setting HDI frequency Reserved Reserved Reserved If the...

Страница 120: ...ning time reaches the value set by P8 17 the digital output terminal outputs ON signal P7 10 Model No Factory default Setting range Inverter model No P7 11 Software version No Factory default Setting...

Страница 121: ...5535h Display the accumulated power on time after production When this time reaches the value set by P8 17 the inverter multifunctional digital output function 24 outputs ON signal P7 14 Accumulated p...

Страница 122: ...P8 07 Acceleration time 4 Factory default Model depend Setting range 0 1s 3600 0s P8 08 Deceleration time 4 Factory default Model depend Setting range 0 1s 3600 0s KE300A series inverter supplies 4 k...

Страница 123: ...quency is decreased to zero It is the time taken by the motor to change its spinning direction when the inverter receives REV command during its running process The time is shown in Figure 6 14 Dead t...

Страница 124: ...ing command is valid for example the terminal running command is close before power on the inverter will not response the running command After the running command is removed valid again the inverter...

Страница 125: ...m P8 22 Jump frequency during ACC DEC Factory default 0 Setting range 0 Invalid 1 Valid It is used to set if jump frequency is valid during ACC DEC When valid the running frequency is in the range of...

Страница 126: ...ime 1 if the running frequency is lower than P8 26 then select DEC time 2 P8 27 Terminal jog priority Factory default 0 Setting range 0 Invalid 1 Valid It is used to set whether the priority of termin...

Страница 127: ...ection signal DO or Relay Frequency detection amplitude Time t Any arrival frequency Output frequency Hz Frequency detection amplitude Figure 6 19 Any arrival frequency detection diagram P8 34 Zero cu...

Страница 128: ...e t Output current over limit detection delay time P8 37 Figure 6 21 Output current over limit function diagram P8 38 Any arrival current 1 Factory default 100 0 Setting range 0 0 300 0 motor rated cu...

Страница 129: ...g running function When P8 42 timing function selection is valid timing starts after the inverter starts reaches the setting timing running time the inverter stops automatically meantime DO terminal o...

Страница 130: ...8 52 Dormancy delay time Factory default 0 0s Setting range 0 0s 3600 0s The parameters are used to achieve dormancy and wake up function in water supply applications During running when the setting f...

Страница 131: ...before the motor overload protection The bigger the parameter is the smaller the pre warning lead is After the accumulated output current is bigger than P9 02 overload inverse time limit curve DO outp...

Страница 132: ...verter is power on If the function is valid the inverter UVW terminals have output voltage after power on for a while P9 09 Fault auto reset times Factory default 0 Setting range 0 5 After the inverte...

Страница 133: ...input terminal is ON the corresponding binary bit is 1 when the input terminal is OFF the corresponding binary bit is 0 All DI statuses are displayed as decimal numbers P9 21 The third fault type outp...

Страница 134: ...e Reserved Ten thousands place Running time arrival E 26 same as units place of P9 47 P9 49 Fault protection action selection 3 Factory default 00000 Setting range Units place Customized fault 1 E 27...

Страница 135: ...P9 54 Running frequency selection continuously when fault Factory default 0 Setting range 0 Run at current running frequency 1 Run at setting frequency 2 Run at upper limit frequency 3 Run at lower l...

Страница 136: ...by P9 61 means that bus voltage returns to normal P9 59 2 When instantaneous power off or voltage drops suddenly the inverter decelerates to stop Running frequency Hz Time t P9 59 2 DEC to stop DEC t...

Страница 137: ...urrent is smaller than off load detection level P9 64 lasts for longer than off load detection time P9 65 the output frequency will reduce to 7 of the rated frequency automatically During off load pro...

Страница 138: ...urce Factory default 0 Setting range 0 PA 01 1 AI1 2 AI2 3 Keypad potentiometer 4 High speed pulse HDI 5 Communication 6 Multi step command PA 01 PID keypad given Factory default 0 0 Setting range 0 0...

Страница 139: ...Factory default 0 000s Setting range 0 00 10 000 Proportional gain Kp1 It decides the adjustment intensity of the whole PID regulator The higher the Kp1 is the stronger the adjustment intensity is Whe...

Страница 140: ...PA 13 PID output filter time Factory default 0 00s Setting range 0 00s 60 00s PA 12 is used to filter the PID feedback value this filter can improve anti interference capability of feedback value but...

Страница 141: ...hen the deviation absolute value between given and feedback is smaller than PA 19 PID parameter switching deviation 1 PID parameter selection is group 1 When the deviation absolute value between given...

Страница 142: ...pectively PA 25 PID integration attribute Factory default 00 Setting range Units place Integration separate 0 Invalid 1 Valid Tens place Stop integrating or not after output reaches limit 0 Continue i...

Страница 143: ...back lost or not When PID feedback is smaller than feedback lost detection value PA 26 lasts for longer than PID feedback lost detection time PA 27 the inverter alarms fault E 31 and handles according...

Страница 144: ...e is 0 the wobble frequency is disabled Figure 6 27 Wobble frequency operation diagram PB 00 Wobble frequency amplitude setting mode Factory default 0 Setting range 0 Relative to the center frequency...

Страница 145: ...ue PB 03 Wobble frequency cycle Factory default 10 0s Setting range 0 1s 3000 0s PB 04 Triangle wave rise time of wobble frequency Factory default 50 0 Setting range 0 1 100 0 Wobble frequency cycle I...

Страница 146: ...es PB 08 DO outputs setting counting value arrival ON signal then the counter will stop counting When the counting value reaches PB 09 DO outputs designated counting value ON signal The counter will c...

Страница 147: ...ange 100 0 100 0 PC 05 Multi step command 5 Factory default 0 0 Setting range 100 0 100 0 PC 06 Multi step command 6 Factory default 0 0 Setting range 100 0 100 0 PC 07 Multi step command 7 Factory de...

Страница 148: ...r details PC 16 PLC running mode Factory default 0 Setting range 0 Stop after one cycle 1 Keep last frequency after one cycle 2 Circular running When frequency source is set by simple PLC the symbols...

Страница 149: ...on each time PC 18 0th phase running time Factory default 0 0s m Setting range 0 0s m 6500 0s m PC 19 0th Phase ACC DEC time selection Factory default 0 Setting range 0 3 PC 20 1st Phase running time...

Страница 150: ...0 0s m Setting range 0 0s m 6500 0s m PC 37 9th Phase ACC DEC time selection Factory default 0 Setting range 0 3 PC 38 10th Phase running time Factory default 0 0s m Setting range 0 0s m 6500 0s m PC...

Страница 151: ...hour PC 51 Multi step command 0 given mode Factory default 0 Setting range 0 PC 00 1 AI1 2 AI2 3 Keypad potentiometer 4 HDI High speed pulse HDI 5 PID control 6 Keypad setting frequency P0 08 UP DN c...

Страница 152: ...ing motor parameters After PP 01 is set to 1 most of the inverter function parameters are restored to the factory default settings except motor parameters frequency command decimal place P0 22 fault r...

Страница 153: ...code parameter can be modified or not is used to protect function parameter being modified improperly When the function code is set to 0 all the function codes can be modified when the function code...

Страница 154: ...rminal is valid the control mode is determined by A0 00 value reverse When torque control prohibit terminal is valid the control mode is speed control A0 01 Torque setting source selection in torque c...

Страница 155: ...ation time Factory default 0 00s Setting range 0 00s 36000s The speed variation rate of the motor and load is determined by the difference between the motor output torque and the load torque in torque...

Страница 156: ...ion that an inverter drives 4 pumps A9 01 Auxiliary pump 1 Factory default 0 Setting range 0 Disable 1 Enable A9 02 Auxiliary pump 1 Start and stop delay Factory default 0 Setting range 0 0 3600 0S A9...

Страница 157: ...KE300A Inverter Parameter Description 154 Figure 6 30 Constant pressure water supply logic diagram Figure 6 31 Constant pressure water supply wiring diagram...

Страница 158: ...ng last started power frequency pump stops working and the principle is first start and then stop A9 07 Double speed over current stall action current compensation coefficient Factory default 40 Setti...

Страница 159: ...ng range 1 200 PID adjustment is too slow in some applications adjust this parameter PID output value the original PID output value this parameter A9 09 AO1 output analog signal selection Factory defa...

Страница 160: ...03 displays the output voltage of inverter at run time Code Name Range U0 04 Output current 0 00A 655 35A Rated Power 55kW 0 0A 6553 5A Rated Power 55kW U0 04 displays the output current of inverter a...

Страница 161: ...low level open then the bit is set to 0 The relationship between Digital value output terminal and binary code is shown below Bit0 Bit1 Bit2 Bit3 DO3 Relay 1 Relay 2 DO1 Bit4 Bit5 Bit6 Bit7 DO2 Code N...

Страница 162: ...step when inverter is running in simple PLC mode The relationship between displayed value and current step is shown below Displayed value Inverter is running at step X 1 X 0 2 X 1 F X 15 Code Name Ran...

Страница 163: ...ays the sampling linear velocity of High speed pulse input HDI The unit is meter per minute m min It can be calculated according to number of the actual sampling pulse and PB 07 number of pulse per me...

Страница 164: ...or temperature 0 200 U0 43 displays the current temperature of motor NOTE This code is reserved not available in present Code Name Range U0 35 Target torque 200 200 U0 43 displays the current upper li...

Страница 165: ...ame Range U0 43 DO input status visual display 1 U0 43 displays whether intuitive display function 1 40 are valid or not There are 5 digital tubes on keypad Every digital tube has 8 segments and each...

Страница 166: ...turers Code Name Range U0 45 Reserved U0 58 Reserved Code Name Range U0 59 Setting frequency 100 100 U0 60 Running frequency 100 100 U0 59 displays current setting frequency U0 60 displays current run...

Страница 167: ...pulse group interference rejection ESD interference rejection and power low frequency end interference rejection specific test items including 1 Interference rejection tests of input voltage sag inter...

Страница 168: ...nces it can be handled by referring to the following methods 1 For the measuring meters receivers and sensors their signals are generally weak If they are placed nearby the inverter or together with t...

Страница 169: ...may cause resonance and thus result in leakage current If thermal relay is used it may generate error action The solution is to reduce the carrier frequency or install output reactor It is recommende...

Страница 170: ...he cables are connected well 5 Ask for technical support 6 Ask for technical support 7 Ask for technical support Fault Name Over current when acceleration Fault Code E 02 Reason 1 Short circuit or gro...

Страница 171: ...t speed running Fault Code E 04 Reason 1 Short circuit or ground fault occurred at inverter output 2 Control mode is vector control motor parameters are not identified 3 The voltage is too low 4 Load...

Страница 172: ...h 2 There is external force driving the motor to run during the inverter running Solution 1 Make the voltage in the normal range 2 Cancel the external force or install braking resistor Fault Name Powe...

Страница 173: ...ault Name Input phase failure Fault Code E 12 Reason 1 The input three phase power supply is abnormal 2 The power board is abnormal 3 The control board is abnormal 4 The thunder prevention board is ab...

Страница 174: ...t Name Peripheral device fault Fault Code E 15 Reason 1 DI terminal receives an external fault signal generated by peripheral device Solution 1 Reset running Fault Name Communication fault Fault Code...

Страница 175: ...Replace the main board Fault Name Inverter hardware fault Fault Code E 22 Reason 1 Over voltage 2 Over current Solution 1 Handle as over voltage fault 2 Handle as over current fault Fault Name Short c...

Страница 176: ...ult Code E 30 Reason 1 The inverter running current is smaller than P9 64 Solution 1 Confirm if the load breaks away and P9 64 P6 65 are set properly Fault Name PID feedback lost fault when running Fa...

Страница 177: ...the inverter runs Motor and motor cables are abnormal The inverter parameters are set improperly motor parameter The connection of the cables of the power board and control board are not good The pow...

Страница 178: ...There provide asynchronous series and half duplex transmission mode At the same time just one can send the data and the other only receives the data between master and slave In the series asynchronou...

Страница 179: ...than 3 5 bytes interval following a previous message the receiving device will consider it as a continuation of the previous message Because of the frame s confusion at last the CRC value is incorrec...

Страница 180: ...e 97H CRC High byte ADH Slave responding information Address 02H Command Code 06H Data Address High byte F0H Data Address Low byte 0AH Data Content High byte 13H Data Content Low byte 88H CRC Low byte...

Страница 181: ...final contents of the register after all the bytes of the message have been applied is the CRC value When the CRC is appended to the message the low byte is appended first followed by the high byte Th...

Страница 182: ...to zero Corresponding function code addresses are indicated below P0 PF group parameter address High byte 00 to FF low byte 00 to FF A0 group parameter address High byte 40 low byte 00 to FF U0 group...

Страница 183: ...is 1Hz 101D Communication setting value 101E Actual feedback speed 101F Main frequency A display 1020 Auxiliary frequency B display Note Communication setting value is the percentage of relative value...

Страница 184: ...rol write only Command Address Command Content 2003 0 7FFF refers to 0 100 9 Pulse output control write only Command Address Command Content 2004 0 7FFF refers to 0 100 10 This function is required wh...

Страница 185: ...nverter overload 000B Motor overload 000C Input phase failure 000D Output phase failure 000E Module overheat 000F External fault 0010 Communication fault 0011 Contactor fault 0012 Current detection fa...

Страница 186: ...er baud rate is the faster communication is Pd 01 Data Format Factory Setting 0 Setting range 0 No check Data format 8 N 2 1 Even parity Check data format 8 E 1 2 Odd Parity Check data format 8 O 1 3...

Страница 187: ...eout the system will report communication failure error Err16 At normal circumstances it is set to be invalid If in the continuous communication system set the parameter you can monitor the communicat...

Отзывы: