KE300A Inverter Parameter Description
115
P7-04
Running status display 2
Factory default
0
Setting
range
0000
~
FFFF
7
6
5
4
3
2
1
0
PID feedback
PLC phase
HDI frequency(kHz)
Running frequency 2(Hz)
Remain running time
AI1 voltage before calibration(V)
AI2 voltage before calibartion(V)
Reserved
15 14 13 12 11 10 9
8
Linear speed
Current power-on time(Hour)
Current running time(Min)
HDO frequency(kHz)
Communication setting value
Reserved
Main frequency A display (Hz)
Auxiliary frequency B display(Hz)
If the above parameters need to be displayed when running, set
the corresponding positions to 1, and change the binary
numbers into hexadecimal numbers, and then enter them into
P7-04.
Operation display parameter is used to set the parameters which can be viewed when running.
There are at most 32 parameters can be viewed, set the status parameters via the binary bits of P7-03 and
P7-04, and the display sequence starts from the lowest order of P7-03.