KE300A Inverter Parameter Description
116
P7-05
Stop status display
Factory default
0
Setting
range
0000
~
FFFF
7
6
5
4
3
2
1
0
Setting frequency(Hz)
Bus voltage(V)
DI input status
DO output status
AI1 voltage(V)
AI2 voltage(V)
Radiator temperature
Count value
15 14 13 12 11 10 9
8
Length value
PLC phase
Load speed
PID setting
HDI frequency
Reserved
Reserved
Reserved
If the above parameters need to be displayed when stop, set
the corresponding positions to 1, and change the binary
numbers into hexadecimal numbers, and then enter them into
P7-05.