KE300A Inverter Parameter Description
149
Group PD Communication Parameters
Refer to the Communication Protocol for details.
Group PP Function Code Management
PP-00
User password
Factory default
0
Setting range
0 ~ 65535
Any non-zero number can be set, and then the password protection function will be enabled. When user
enters into the menu next time, “-----” will be displayed, please input the right password, otherwise the
parameters cannot be checked or modified.
0000: Clear the previous password and disable the password protection function.
PP-01
Parameter initialization
Factory default
0
Setting range
0
No operation
1
Restore factory default, but not including motor parameters
2
Clear the fault record
1. Restore to factory default, but not including motor parameters.
After PP-01 is set to 1, most of the inverter function parameters are restored to the factory default settings,
except motor parameters, frequency command decimal place (P0-22), fault record information,
accumulated running time (P7-09), accumulated power on time (P7-13), accumulated power consumption
(P7-14).
2. Clear the record information.
Clear the fault record information, accumulated running time (P7-09), accumulated power on time (P7-13),
accumulated power consumption (P7-14).
PP-02
Function parameter group
display selection
Factory default
00
Setting range
Units
l
U0 group display selection
0
No display
1
Display
Tens
A0 group display selection
0
No display
1
Display
PP-03
Reserved
The setting of parameter display mode is convenient for users to view the function parameter of different
spread patterns according to the actual demand.
PP-04
Function code modification attribute
Factory default
0
Setting range
0
Valid
1
Invalid