KE300A Inverter Parameter Description
117
P7-06
Load speed display coefficient
Factory default
3.0000
Setting range
0.0001 ~ 6.5000
The correspondence of the inverter output frequency and the load speed can be adjusted via this
parameter when the load speed needs to be displayed.
P7-07
IGBT module temperature
Factory default
-
Setting range
0.0
℃
~ 100.0
℃
Display IGBT module temperature.
The over temperature protection values of different IGBT modules are not the same.
P7-08
Inverter rated voltage
Factory default
Model depend
Setting range
1V~2000V
Display inverter rated voltage.
P7-09
Accumulated running time
Factory default
-
Setting range
0h ~ 65535h
Display the accumulated running time of the inverter. When the running time reaches the value set by
P8-17, the digital output terminal outputs ON signal.
P7-10
Model No.
Factory default
-
Setting range
Inverter model No.
P7-11
Software version No.
Factory default
-
Setting range
Control software version No.
P7-12
Load speed display decimal place
Factory default
0
Setting range
0
0 decimal place
1
1 decimal place
2
2 decimal places
3
3 decimal places
The parameters are used to set load speed display decimal place. The following load speed calculation
format for example:
If load speed display factor (P7-06) is 2.000, load speed decimal place (P7-12) is 2 (2 decimal places),
when the running frequency is 40.00Hz, load speed is: 40.00
×
2.000=80.00 (2 decimal places displayed)
If the inverter stops, load speed is displayed as setting frequency corresponding speed, namely “setting
load speed”. If setting frequency=50.00Hz, the stop status load speed is: 50.00×2.000=100.00 (2 decimal
places displayed)