KE300A Inverter Parameter Description
130
Three phase 220V
≥
7.5kW
Three phase 380V
≥
11kW
Three phase 480V
≥
11kW
Three phase 660V
All
P9-13
Output phase failure protection selection
Factory default
1
Setting range
0: Invalid 1: Valid
Select to protect output phase failure or not.
P9-14
The first fault type
0 ~ 50
P9-15
The second fault type
P9-16
The third (last) fault type
It is used to record the fault types of last three times: 0 indicates no fault, please refer to Chapter 8 for
solutions.
P9-17
The third fault frequency
The last fault frequency
P9-18
The third fault current
The last fault current
P9-19
The third (last) fault bus voltage
The last fault bus voltage
P9-20
The third fault type output
terminal status
The last fault type output terminal status,
sequence: when the input terminal is ON, the
corresponding binary bit is 1, when the input
terminal is OFF, the corresponding binary bit
is 0. All DI statuses are displayed as decimal
numbers.
P9-21
The third fault type output terminal
The last fault type output terminal status,
sequence: when the input terminal is ON, the
corresponding binary bit is 1, when the input
terminal is OFF, the corresponding binary bit
is 0. All DO statuses are displayed as decimal
numbers.
P9-22
The third fault inverter status
The last fault inverter status
P9-23
The third (last) fault power on time
The last fault power on time
P9-24
The third (last) fault running time
The last fault running time
P9-27
The second fault frequency
Same as P9-17 ~ P9-24
P9-28
The second fault current
P9-29
The second fault bus voltage
P9-30
The second fault input terminal status
P9-31
The second fault output terminal status
P9-32
The second fault inverter status
P9-33
The second fault power on time
P9-34
The second fault running time